Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 253 -
4.3) The laying of branch part:
At the same system, the laying form of shunt-wound outdoor units: the outdoor units are on the
same level, the branch joints for the outdoor units are on the same level, the T-shaped pipes for
connecting the balance pipes are installed vertically.
The laying form of Y-shaped branch pipes for shunt-wound outdoor units: Laying horizontally.
The laying form of T-shaped branch pipes for shunt-wound outdoor units: Laying horizontally.
The laying form of Y-shaped branch pipes for indoor units:
1)
Laying horizontally. (the allowable deflection angle
α
=30°
(
-15°
~
+15°
)
2)
Laying horizontally
4.4) Size of tubing connection
Capacity of indoor
units(HP)
Gas side
Liquid side
≥56
Φ
15.9(Flaring nut)
Φ
9.5 (Flaring nut)
≤45
Φ
12.7(Flaring nut)
Φ
6.4(Flaring nut)