Installation
___________________________________________________________________________________
___________________________________________________________________________________
- 255 -
4.5.5 Refrigerant fastness, the Refrigerant fastness, the distance between the supports of
the cross direction tube (copper tube):
Nominal diameter
Below 16
16—25
Above 32
Max. Distance (m)
1.0
1.5
2.0
4.5.6 Calculation of the pipe length
(1) Available length of pipe =pipe the amounts of branch × branch equivalent length
+the amounts of elbow × elbow equivalent length.
(2) Conversion of the branch equivalent length: Convert into the direct pipe length according to
branch part 0.5m/l
(3) Conversion of elbow equivalent length.
Liquid pipe
dimension
Φ
6.35
Φ
9.5
Φ
12.7
Φ
15.9
Φ
19.0
Φ
22.0
Φ
25.0
Φ
28.6
Φ
38.0
Φ
45.0
Φ
54.0
Φ
67
Junction(90°elbow) 0.1 0.15 0.2 0.25
0.3 0.4 0.45
0.5 0.55 0.6 0.65 0.7
4.6) Installation work of Refrigerant pipe
4.6.1 Protection of Refrigerant pipe material
1) Transportation and storing of refrigerant pipe
When transporting the pipes, please protect the pipes from wending and distortion. Please
place a cap at the open end of the pipe in order to prevent water and mud entering, and store in
the appointed site.
3)
All the open tips of the pipes need to be protected. The best feasible means is Enveloping
End, and you can select the easy means of Wrapping. Refer to the following table to select
the means used in different sites.
4)
Site Period
Maintenance
Means
Above three months
Envelop End
Outdoor
Below three months
Envelop End or Wrapping
Indoor
No limit
Envelop End or Wrapping
Summary of Contents for R-410A
Page 103: ...Wall mount 102 Part 4 2 Wall Mounted...
Page 113: ...Wall mount 112 4 Dimensions 4 1 YDS 22 36EC 4 2 YDS 45 56EC...
Page 115: ...Wall mount 114 5 Piping Diagrams 5 1 YDS 22 56EC 5 2 YDS 22 56HC...
Page 116: ...Wall mount 115 6 Wiring diagrams 6 1 YDS 22 36EC 6 2 YDS 45 56EC...
Page 117: ...Wall mount 116 6 3 YDS 22 56HC...
Page 118: ...Wall mount 117 7 Sound level 7 1 Test condition 7 2 Noise spectrums YDS 22 36EC HC...
Page 119: ...Wall mount 118 YDS 45 56EC HC...
Page 120: ...Wall mount 119 8 Velocity temperature distribution Discharge angle 70...