FORM 160.55-O1 (604)
121
YORK INTERNATIONAL
3
YORK HISTORY 1
CHILLER ID 0
---------------------------------------------------------------------------
© 1997 - 1999 YORK INTERNATIONAL COR
PO
RA
TION
MSYSTEM READY TO START
LCSSS – LOGIC BOARD POWER SUPPLY
[List any warnings that were active at the time of
shutdown]
Controls C.MLM.02.03.102
Run Time 0 Days 2 Hr 59 Min
Operating Hours = 294 Hr
Number Of Starts = 105
Control Source = Local
Evaporator
---------------------------------------------------------------------------
Leaving Chilled Active Setpoint = 45.0 ~F
Chilled Liquid Pump = Stop
Chilled Liquid Flow Switch = Open
Leaving Chilled Liquid Temperature = 50.0 ~F
Return Chilled Liquid Temperature = 59.3 ~F
Evaporator Pressure = 7.2 Psia
Evaporator Saturation Temperature = 41.1 ~F
Evaporator Refrigerant Temperature = 40.0 ~F
[If Refrigerant Sensor enabled]
Small Temperature Difference = 10.0 ~F
Condenser
---------------------------------------------------------------------------
Condenser Liquid Pump = Stop
Condenser Liquid Flow Switch = Open
Leaving Condenser Liquid Temperature = 85.0 ~F
Return Condenser Liquid Temperature = 94.9 ~F
Condenser Pressure = 13.8 Psia
Condenser Saturation Temperature = 71.7 ~F
Small Temperature Difference = -13.3 ~F
Drop Leg Refrigerant Temperature = 85.0 ~F
[If Drop Leg Sensor enabled]
Sub Cooling Temperature = 2.0 ~F
[If Drop Leg Sensor enabled]
Compressor
---------------------------------------------------------------------------
Discharge Temperature = 121.6 ~F
Vent Line Solenoid = Off
Oil Sump
---------------------------------------------------------------------------
Oil Pump Run Output = Off
Oil Pressure = 0.0 Psid
Oil Sump Temperature = 137.9 ~F
[Skip the following section if Hot Gas Bypass is not
enabled]
Hot Gas
---------------------------------------------------------------------------
FIG. 48 –
SAMPLE PRINTOUT (HISTORY REPORT)
Valve Position [If Hot Gas enabled] = 0 %
Pre-Rotation Vanes Position = 0 %
Surge
---------------------------------------------------------------------------
Total Surge Count = 127
Surge Window Time = 1 Min
Surge Window Count = 0
[Skip the following section if Liquid Level is not
enabled]
Refrigerant Level Control
---------------------------------------------------------------------------
Refrigerant Level Position = 35 %
Ramp Up Time Remaining = 15 Sec
[If Ramp Up in effect]
Purge Control
---------------------------------------------------------------------------
Pressure = 42.8 Psia
Exhaust Count = 0
Exhaust Window = 60 Min
[Skip the following section if Motor Type is not EM]
Electro-Mechanical Starter
---------------------------------------------------------------------------
Motor Run = Off
% Full Load Amps = 0 %
[Skip the following section if Motor Type is not Mod A
SSS]
Liquid-Cooled Solid State Starter
---------------------------------------------------------------------------
Motor Run = Off
% Full Load Amps = 0 %
Phase A Voltage = 447 V
Phase B Voltage = 409 V
Phase C Voltage = 442 V
Phase A Current = 0 A
Phase B Current = 0 A
Phase C Current = 0 A
[Skip the following section if Motor Type is not Mod B
SSS]
Liquid-Cooled Solid State Starter
---------------------------------------------------------------------------
Motor Run = Off
% Full Load Amps = 0 %
Starter Model = 33L
KW Hours = 20723 KWH
Input Power = 145 KW
Phase A Voltage = 447 V
Phase B Voltage = 409 V
Phase C Voltage = 442 V
Phase A Current = 0 A
Phase B Current = 0 A