Table 2: 

Airflow data (CFM)

Models

Blower 

motor speed

External static pressure (in. W.C.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

B18B

High (5)

975

925

875

825

800

750

700

650

600

550

Medium high (4)

900

850

800

775

725

675

625

575

525

500

Medium (3)

825

775

725

700

650

600

550

500

450

400

Medium low (2)

650

600

550

500

425

-

-

-

-

-

Low (1)

450

-

-

-

-

-

-

-

-

-

B24C

High (5)

1150

1125

1100

1050

1025

975

950

900

875

850

Medium high (4)

1000

950

925

875

825

775

750

700

650

600

Medium (3)

775

725

675

625

575

525

450

400

-

-

Medium low (2)

675

600

550

500

425

-

-

-

-

-

Low (1)

525

450

-

-

-

-

-

-

-

-

B30D

High (5)

1150

1125

1075

1050

1025

975

950

925

875

850

Medium high (4)

1000

950

900

875

825

800

750

700

675

625

Medium (3)

775

725

700

650

600

550

500

450

400

-

Medium low (2)

650

600

550

500

450

400

-

-

-

-

Low (1)

575

525

475

400

-

-

-

-

-

-

B36D

High (5)

1500

1475

1450

1425

1425

1400

1375

1350

1325

-

Medium high (4)

1325

1300

1275

1250

1225

1200

1175

1150

1125

1100

Medium (3)

975

950

900

875

825

800

750

700

675

625

Medium low (2)

925

875

825

800

750

700

675

625

575

550

Low (1)

650

600

550

500

450

400

-

-

-

-

C36D

High (5)

1600

1575

1525

1500

1450

1425

1400

1350

1325

1275

Medium high (4)

1400

1375

1325

1275

1225

1200

1150

1100

1075

1025

Medium (3)

1100

1050

1000

950

900

850

800

725

675

625

Medium low (2)

950

900

825

775

725

650

600

550

475

425

Low (1)

725

650

575

525

450

375

-

-

-

-

C42F

High (5)

1525

1500

1450

1425

1375

1350

1300

1275

1225

1200

Medium high (4)

1375

1325

1300

1250

1200

1150

1125

1075

1025

975

Medium (3)

1050

1000

950

900

850

775

725

675

625

575

Medium low (2)

925

875

800

750

700

625

575

525

450

400

Low (1)

700

625

575

500

425

-

-

-

-

-

C48G

High (5)

1925

1900

1875

1850

1800

1775

1750

1725

1700

1675

Medium high (4)

1750

1700

1675

1650

1600

1575

1550

1500

1475

1450

Medium (3)

1400

1350

1300

1275

1225

1175

1125

1075

1050

1000

Medium low (2)

1200

1150

1100

1050

1000

925

875

825

775

725

Low (1)

925

875

800

750

700

625

575

500

450

375

D48G

High (5)

2050

2000

1975

1950

1900

1875

1850

1800

1775

1750

Medium high (4)

1850

1800

1775

1725

1700

1650

1625

1575

1550

1500

Medium (3)

1625

1600

1550

1500

1450

1425

1375

1325

1275

1250

Medium low (2)

1275

1200

1150

1100

1050

975

925

875

825

750

Low (1)

1000

925

875

800

750

675

600

550

475

400

C60H

High (5)

1925

1900

1875

1850

1825

1775

1750

1725

1700

1675

Medium high (4)

1750

1725

1675

1650

1625

1575

1550

1525

1475

1450

Medium (3)

1375

1350

1300

1250

1225

1175

1125

1100

1050

1000

Medium low (2)

1200

1150

1100

1050

1000

950

900

850

800

750

Low (1)

950

900

825

775

725

650

600

550

475

425

D60H

High (5)

1925

1900

1875

1825

1800

1775

1750

1700

1675

1650

Medium high (4)

1775

1750

1725

1675

1650

1600

1575

1525

1500

1450

Medium (3)

1450

1400

1325

1275

1225

1175

1125

1075

1025

975

Medium low (2)

1225

1175

1125

1050

1000

950

875

825

775

700

Low (1)

975

900

850

775

700

625

550

475

425

-

Continued on next page

Table 2: 

Airflow data (CFM) (continued)

Notes: 

1.

No electric heat installed

2.

Air handler units are tested to UL60335-2-40 standards up to 0.6 in. W.C. external static pressure.

3.

Dry coil conditions only; tested without filters

4.

For optimal performance, external static pressures of 0.2 in. W.C. to 0.5 in. W.C. are recommended. Heating applications are tested at 0.5 in. W.C. external static pressure.

5.

Airflow data shown is from testing performed at 230 V. These units use a standard ECM constant torque motor and there is minimal variation of airflow at other distribution
voltage values. The above data can be used for airflow at other distribution voltages.

Clearances 

It is essential to provide the following clearances:

1.

Refrigerant piping and connections - minimum 12 in.

2.

Maintenance and servicing access - minimum 36 in. from the front of
the unit for blower motor or coil replacement

3.

Condensate drain lines routed to clear filter and panel access

4.

Filter removal - minimum 36 in.

5.

The supply air ductwork connected to this unit is designed for 1 in.
clearance for the first 18 in. of combustible materials if an electric heat
kit accessory is installed.

6.

A combustible floor base accessory is available for downflow applica-
tions of this unit, if required by local code.

External duct static

Measure the supply air static pressure. Record this positive number.
Measure the return air static pressure. Record this negative number.
Treat the negative number as a positive and add the two numbers
together to determine the total external system static pressure. If a filter
rack is installed on the return air end of the air handler or indoor coil
section, make sure to measure the return air duct static between the filter
and the indoor coil.

Figure 2:  

Duct static measurements

Models

Blower 

motor speed

External static pressure (in. W.C.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

D60J

High (5)

2100

2075

2050

2025

2000

1975

1925

1900

1875

1850

Medium high (4)

1925

1900

1875

1825

1800

1775

1725

1700

1675

1650

Medium (3)

1750

1725

1675

1650

1600

1575

1525

1500

1450

1425

Medium low (2)

1350

1275

1225

1175

1125

1075

1025

975

925

875

Low (1)

1200

1150

1100

1025

975

925

850

800

750

675

Take measurements here if using
a filter rack.
Return air static must be taken
between the filter and indoor coil.

A1704-001

Table 3: 

Electrical heat - minimum fan speed

Heater kit

models

1,2

Nominal 

kW

at 240 V

Air handler models

B18B

B24C

B30D

B36D

C36D

C42F

C48G

D48G

C60H

D60H

D60J

8HK(0,1)6500206

2.4

Medium 

Low (2)

Medium 

(3)

Medium 
High (4)

Medium 

(3)

Medium 

(3)

Medium 

(3)

Medium 

Low (2)

Medium 

Low (2)

Medium 

Low (2)

Medium 

Low (2)

Medium 

Low (2)

8HK(0,1)6500506

4.8

Medium 

(3)

Medium 

(3)

Medium 
High (4)

Medium 

(3)

Medium 

(3)

Medium 

(3)

Medium 

Low (2)

Medium 

Low (2)

Medium 

Low (2)

Medium 

Low (2)

Medium 

Low (2)

8HK(0,1)6500806

7.7

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 

(3)

Medium 

(3)

Medium 

(3)

Medium 

(3)

Medium 

Low (2)

8HK(0,1)6501006

8HK06501025

9.6

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 

(3)

Medium 

(3)

Medium 
High (4)

Medium 

(3)

Medium 

Low (2)

8HK(1,2)6501506

8HK06501525

14.4

-

Medium 
High (4)

High (5)

Medium 
High (4)

Medium 
High (4)

Medium 
High (4)

Medium 

(3)

Medium 

(3)

Medium 
High (4)

Medium 
High (4)

Medium 

(3)

8HK(1,2)6502006

8HK16502025

19.2

-

-

High (5)

Medium 
High (4)

High (5)

High (5)

Medium 
High (4)

Medium 

(3)

Medium 
High (4)

Medium 
High (4)

Medium 

(3)

8HK(1,2)6502506

8HK16502525

24

-

-

-

-

-

-

-

-

-

Medium 
High (4)

Medium 

(3)

1. (0,1) - 0 = no service disconnect or 1 = with service disconnect
2. (1,2) - 1 = with service disconnect, no breaker jumper bar or 2 = with service disconnect and breaker jumper bar