JOHNSON CONTROLS
21
FORM 102.20-N1
ISSUE DATE: 7/06/2016
3
DELIVERY AND STORAGE
To ensure consistent quality and maximum reliability,
all AHUs are tested and inspected before leaving the
factory.
Short Term
Indoor AHUs: Under no circumstances
should outdoor storage be used.
• Remove of ventilate wrapping to prevent
condensation.
Outdoor AHUs: Recover AHUs after in
-
spection or use tarps during storage.
Short term storage is six months or less from date of
shipment. Storage maintenance during this time is usu-
ally limited to the following:
•
Rotate fans every four weeks, starting on the de-
livery date to prevent moisture from damaging
the bearing.
•
If the AHUs are going to be stored out-of-doors,
prior to installation, special care must be taken to
cover and protect the AHUs from:
•
Dust
•
Rain and snow
•
Rodents
•
Construction vehicles and personnel.
•
Condensation / Ventilation required
•
Protect all parts and porous materials from rain
and other sources of moisture. Decontaminate or
replace parts as needed to make sure microbial
growth is not introduced to the AHU.
• Store the AHU on a firm, flat surface to prevent
distortion. Block the AHU off the ground to pro-
tect components from water or ground moisture.
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
Rigging and lifting should only be done by a professional rigger in accordance with a written rig
-
ging and lifting plan. The most appropriate rigging and lifting method will depend on job specific
factors, such as the rigging equipment available and site needs. Therefore, a professional rigger
must determine the rigging and lifting method to be used, and it is beyond the scope of this manual
to specify rigging and lifting details.
LD19197