JOHNSON CONTROLS
41
SECTION 3 - HANDLING, STORAGE, AND INSTALLATION
FORM 102.20-N1
ISSUE DATE: 7/06/2016
3
Setting Up and Pulling Solution XT Sections
Together
Use the following instructions to set up and pull the
sections together.
1.
Place the first section in its final position and an
-
chor or block it before placing the next section.
2. Attach the come-a-longs to the far end of the next
FIGURE 56 -
COME-A-LONG ATTACHED TO A
SECTION
LD13775
COME-A-LONG
Make sure the chain does not apply pres
-
sure to the drain connection. Improper
positioning of the chain may cause dam-
age to the AHU.
3. If the AHU is equipped with an optional expand-
ed cabinet with a structural steel base, remove the
lifting lugs within the shipping split shown in
FIGURE 57 -
REMOVE LIFTING LUGS IN
EXPANDED CABINET
LD14265
LIFTING LUG
BASE
CHANNEL
WELDED-
CHANNEL
FILLER
4. Place the next section on the curb about 8 in. from
the first section.
5. Feed the electrical and control connections from
section to section and make sure that they will be
accessible after the sections are joined as shown
FIGURE 58 -
ELECTRICAL CONNECTOR (NOT
CONNECTED)
LD13373a
CONNECTOR
6. Assemble the electrical connectors and/or pneu-
matic tubes according to their labels before join-
ing the sections as shown in
, if access will be a problem later.
FIGURE 59 -
ELECTRICAL CONNECTORS
(CONNECTED)
LD13374
CONNECTORS
7. After making the electrical and control connec-
tions, and before proceeding with assembly, re-
move and reposition the top shipping split angle