5371951-YTG-C-0919
Johnson Controls Ducted Systems
3
.
All dimensions are in inches and are subject to change without notice.
Overall height is from bottom of mounting feet to top of unit.
Overall length and width include mounting feet and screw heads.
PHYSICAL AND ELECTRICAL DATA
MODEL
TCHE24S41S1
TCHE36S41S1
TCHE48S41S1
Unit Supply Voltage
208-230V, 1
60Hz
Normal Voltage Range
1
1. Rated in accordance with AHRI Standard 110-2012, utilization range “A”.
187 to 252
Minimum Circuit Ampacity
18.3
19.1
24.6
Max. Overcurrent Device Amps
2
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
30
30
40
Min. Overcurrent Device Amps
3
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
20
20
25
Compressor Amps
Type
Scroll
Scroll
Scroll
Rated Load
13.5
14.1
18.5
Locked Rotor
58.3
72.2
124.0
Crankcase Heater
Yes
Yes
Yes
Factory External Discharge Muffler
No
No
No
Factory External Check Valve
No
No
No
HS Kit Required with TXV
4
4. See Hard Start Kit Accessory Installation Manual for Hard Start Kit part number for each model.
No
No
No
Fan Diameter Inches
23
23
23
Fan Motor
Rated HP
1/4
1/4
1/4
Rated Load Amps
1.3
1.3
1.3
Nominal RPM
850
850
850
Nominal CFM
3200
3200
3050
Coil
Face Area Sq. Ft.
11.96
11.96
13.96
Rows Deep
1
1
1
Fins / Inch
23
23
23
Refrigerant Lines
5
5. When more than 50 feet of interconnecting tubing and more than 30 feet of vertical lift is used, consult the Application Data (part number 247077).
For long-line applications, interconnecting lines over 100 feet must be installed with liquid line solenoid.
Max. Length
200
200
200
Max. Lift
65
65
65
Max. Drop
150
150
150
Liquid Line Set OD (Field Installed)
3/8
3/8
3/8
Vapor Line Set OD (Field Installed)
3/4
3/4
7/8
Unit Charge (Lbs. - Oz.)
6
6. The Unit Charge is correct for the outdoor unit, smallest matched indoor unit, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet,
add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
5 - 0
6 - 6
7 - 4
Charge Per Foot, Oz.
0.62
0.62
0.67
Operating Weight Lbs.
195
215
240
B
C
A
DIMENSIONS
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
B
C
Liquid
Vapor
TCHE24S41S1
37-1/4
20
45
3/8
3/4
TCHE36S41S1
37-1/4
20
45
TCHE48S41S1
43-1/4
20
45