Johnson Controls Ducted Systems
PROCEDURES:
1. Check the Factory Unit Charge listed on the unit nameplate to verify the refrigerant charge for the outdoor unit, the smallest matched indoor unit, and
the 15 feet of interconnecting lineset.
2. Verify the indoor metering device and additional charge required for the specific matched indoor unit in the system using the above table.
3. Add additional charge for the amount of interconnecting lineset greater than 15 feet at the rate specified in the Physical and Electrical Table.
4. For installations requiring additional charge, weigh in refrigerant for the specific matching indoor unit and actual lineset length.
5. Once the charge adders for matched indoor unit and for lineset have been weighed in, verify the system operation against the temperatures and pressures in the
Charging Chart for the outdoor unit. Locate Charging Charts on the outdoor unit and also in the Service Data Application Guide on
www.simplygettingthejobdone.com.
Follow the Subcool or Superheat charging procedure in the Installation Manual according to the type of indoor metering device
in the system, and allow ten minutes after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the Charging
Chart.
6. Permanently stamp the unit data plate with the TOTAL SYSTEM CHARGE defined as follows: TOTAL SYSTEM CHARGE = Base Charge (as shipped) + charge
adder for matched indoor unit + charge adder for actual lineset charge adjustments to match the Charging Chart.
SYSTEM CHARGE FOR VARIOUS MATCHED SYSTEMS
System Charge for Various Matched Systems
Outdoor Unit
TCHE24S41S1
TCHE36S41S1
TCHE48S41S1
Required TXV
1,2
BA1
BA2
BA2
Indoor Unit
3,4
,
5
Additional Charge, Oz
CF/CM/CU30(B,C,D)
0
–
–
CF/CM/CU36(A,B,C,D)
7
–
–
FC38C
–
0
–
FC49D
–
–
0
AP30B
0
–
–
AP36C
7
–
–
AE30B
0
–
–
AE36(B,C)
7
–
–
AVC30B
0
–
–
AVC36(B,C)
7
–
–
Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil
only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.
FOOTNOTES:
1. For applications requiring a TXV use S1-1TVM*** series kit.
2. A TXV kit must be used with these indoor units to obtain system performance.
3. Systems matched with furnaces or air handlers not equipped with blower-off delays may require 60 second time delay.
4. CF and FC coils cannot be used in horizontal applications.
5. Charge adders shown above do not indicate that coils are rated for every application. Refer to Performance Data Tables for actual performance for
specified system matches. Obtain certified system ratings from
www.ahridirectory.org
.