background image

400991-YTG-B-0708

2

Johnson Controls Unitary Products

Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.

FRONT

33

A

LEFT SIDE

Combustion Air Inlet

Condensate Drain
(Downflow)

Vent Outlet

Thermostat
Wiring

28.5”

Gas Pipe
Entry

Electrical
Entry

Condensate
Drain

Thermostat
Wiring

RIGHT SIDE

Vent Outlet

Condensate Drain
(Downflow)

14”

1”

1.5”

23”

Combustion Air Inlet

Gas Pipe
Entry

Electrical
Entry

Condensate
Drain

Optional Return Air
Cutout (Either side)

29.5”

C

SUPPLY END

.56”

.56”

20”

B

3”

23.8”

.56”

Combustion
Air Inlet

Vent
Outlet

RETURN END

B

24.25”

Cabinet & Duct Dimensions

BTUH (kW)

Input

Nominal

CFM (m

3

/min)

Cabinet

Size

Cabinet Dimensions (Inches)

Approximate

Operating Weights

A

B

C

Lbs

TG9S040A08MP11

800

A

14 1/2

13 3/8

11 3/4

113

TG9S060A10MP11

1000

A

14 1/2

13 3/8

11 3/4

118

TG9S060B12MP11

1200

B

17 1/2

16 3/8

13 1/4

122

TG9S080B12MP11

1200

B

17 1/2

16 3/8

14 3/4

126

TG9S080C16MP11

1600

C

21

19 7/8

16 1/2

136

TG9S080C22MP11

2200

C

21

19 7/8

16 1/2

139

TG9S100C16MP11

1600

C

21

19 7/8

18 1/4

142

TG9S100C20MP11

2000

C

21

19 7/8

18 1/4

145

TG9S120D16MP11

1600

D

24 1/2

23 3/8

21 3/4

153

TG9S120D20MP11

2000

D

24 1/2

23 3/8

21 3/4

156

TG9S130D20MP11

2000

D

24 1/2

23 3/8

No Hole

160

Ratings & Physical / Electrical Data

Input

Output

Nominal

Airflow

Total Unit

Amps

AFUE

Air Temp. 

Rise

Max 

Over-Current 

Protect

Min. wire Size 

(awg) @ 75 ft 

one way

Max. Outlet

Air Temp

MBH

CFM

°F

°F

TG9S040A08MP11

38

800

8.0

95.5

30-60

15

14

155

TG9S060A10MP11

57

1000

10.0

95.5

30-60

15

14

155

TG9S060B12MP11

57

1200

10.0

95.5

30-60

15

14

160

TG9S080B12MP11

76

1200

10.0

95.5

35-65

15

14

165

TG9S080C16MP11

76

1600

11.5

95.5

35-65

15

14

155

TG9S080C22MP11

76

2200

17.0

95.5

35-65

20

12

155

TG9S100C16MP11

95

1600

11.5

95.5

35-65

15

14

165

TG9S100C20MP11

95

2000

17.0

95.5

35-65

20

12

155

TG9S120D16MP11

114

1600

11.5

95.5

40-70

15

14

170

TG9S120D20MP11

114

2000

17.0

95.5

35-65

20

12

160

TG9S130D20MP11

123.5

2000

17.0

95.5

45-75

20

12

165

Summary of Contents for TG9S

Page 1: ...to install ideal height 33 tall cabinet Blower off delay for cooling SEER improvement Easy access to controls to connect power control wiring Built in high level self diagnostics with fault code displays standard on integrated control module for reliable operation Low unit amp requirement for easy replacement application Single wire twinning or staging feature available All models are convertable ...

Page 2: ...13 TG9S060A10MP11 1000 A 14 1 2 13 3 8 11 3 4 118 TG9S060B12MP11 1200 B 17 1 2 16 3 8 13 1 4 122 TG9S080B12MP11 1200 B 17 1 2 16 3 8 14 3 4 126 TG9S080C16MP11 1600 C 21 19 7 8 16 1 2 136 TG9S080C22MP11 2200 C 21 19 7 8 16 1 2 139 TG9S100C16MP11 1600 C 21 19 7 8 18 1 4 142 TG9S100C20MP11 2000 C 21 19 7 8 18 1 4 145 TG9S120D16MP11 1600 D 24 1 2 23 3 8 21 3 4 153 TG9S120D20MP11 2000 D 24 1 2 23 3 8 2...

Page 3: ...BR0614 For 14 1 2 cabinets S1 1BR0517 or 1BR0617 For 17 1 2 cabinets S1 1BR0521 or 1BR0621 For 21 cabinets S1 1BR0524 or 1BR0624 For 24 1 2 cabinets 1BR05xx series are galvanized steel filter racks 1BR06xx are pre painted steel filter racks to match the appearance of the furnace cabinet COMBUSTIBLE FLOOR BASE KIT For installation of these furnaces in downflow applications directly onto combustible...

Page 4: ...232 1313 1291 1280 1250 1209 1207 1148 1055 937 Low 826 821 853 858 838 817 794 776 760 711 TG9S080C22MP11 High 2529 2435 2338 2256 2162 2041 1920 1794 1654 1501 Medium High 2166 2111 2070 2001 1927 1849 1719 1614 1499 1344 Medium Low 1697 1685 1664 1631 1586 1531 1466 1393 1315 1185 Low 1383 1377 1358 1336 1285 1244 1199 1147 1048 925 TG9S100C16MP11 High 1909 1880 1823 1776 1706 1637 1562 1474 13...

Page 5: ...1209 Medium High 1543 1543 1516 1504 1477 1446 1382 1309 1202 1099 Medium Low 1238 1241 1243 1241 1252 1242 1201 1140 1074 967 Low 906 902 903 910 888 866 859 829 795 743 TG9S080C22MP11 High 2585 2492 2405 2321 2232 2137 2015 1902 1745 1577 Medium High 2098 2067 2036 1982 1928 1860 1767 1670 1549 1331 Medium Low 1619 1628 1614 1584 1545 1488 1424 1339 1216 1121 Low 1338 1347 1327 1301 1262 1199 11...

Page 6: ... change without notice Printed in U S A 400991 YTG B 0708 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 400991 YTG A 0608 Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 ...

Reviews: