5532522-UIM-B-0619

Johnson Controls Ducted Systems

7

SECTION III: FILTERS

FILTER INSTALLATION

All applications require the use of a field installed filter. All filters and
mounting provision must be field supplied.
Filters must be installed external to the furnace cabinet. 

DO  NOT

attempt to install filters inside the furnace.

1. Air velocity through throwaway type filters may not exceed 300 feet per 

minute (91.4 m/min). All velocities over this require the use of high velocity 

filters.

2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For 

CFM greater than 1800, you may use two side returns or one side and the 
bottom or one return with a transition to allow use of a 20x25 filter.

SIDE RETURN

Locate the “L” shaped corner locators. These indicate the size of the cut-
out to be made in the furnace side panel. Refer to Figure 7.

Install the side filter rack following the instructions provided with that
accessory. If a filter(s) is provided at another location in the return air
system, the ductwork may be directly attached to the furnace side
panel.

HORIZONTAL FILTERS

Any branch duct (rectangular or round duct) attached to the plenum
must attach to the vertical plenum before the filter. Use of straps and/or
supports is required to support the weight of the external filter box.

SECTION IV: GAS PIPING

GAS SAFETY

GAS PIPING INSTALLATION

Properly sized wrought iron, approved flexible or steel pipe must be
used when making gas connections to the unit. If local codes allow the
use of a flexible gas appliance connection, always use a new listed con-
nector. Do not use a connector that has previously serviced another gas
appliance.
Some utility companies or local codes require pipe sizes larger than the
minimum sizes listed in these instructions and in the codes. The furnace
rating plate and the instructions in this section specify the type of gas
approved for this furnace - only use those approved gases. The instal-
lation of a drip leg and ground union is required. Refer to Figure 9.

 CAUTION

All filters and mounting provision must be field supplied. All installa-
tions must have a filter installed.

NOTICE

Single side return above 1800 CFM is approved as long as the filter
velocity does not exceed filter manufacturer’s recommendation.

Table 3: 

Recommended Filter Sizes (High Velocity 600 FPM)

CFM

(m³/min)

Cabinet

Size

Side

(in)

Bottom

(in)

1200 (34.0)

A

16 x 25

14 x 25

1600 (45.3)

C

16 x 25

20 x 25

2000 (56.6)

C

(2) 16 x 25

20 x 25

 FIGURE 7: 

Side Return Cutout Markings

!

)52172)
)851$&(

&251(5
0$5.,1*6

6,'(2)
)851$&(

$

IMPORTANT:  

Some accessories such as electronic air cleaners and

pleated media may require a larger side opening. Follow the instruc-
tions supplied with that accessory for side opening requirements. Do
not cut the opening larger than the dimensions shown in Figure 6.

 DANGER

An overpressure protection device, such as a pressure regulator,
must be installed in the gas piping system upstream of the furnace
and must act to limit the downstream pressure to the gas valve so it
does not exceed 0.5 PSI (14" w.c., 3.48 kPa). Pressures exceeding
0.5 PSI (14” w.c., 3.48 kPa) at the gas valve will cause damage to the
gas valve, resulting in a fire or explosion or cause damage to the fur-
nace or some of its components that will result in property damage
and loss of life.

 FIGURE 8: 

Gas Valve

IMPORTANT:  

Plan your gas supply before determining the correct

gas pipe entry. Use 90-degree service elbow(s), or short nipples and
conventional 90-degree elbow(s) to enter through the cabinet access
holes.

!

INLET

WRENCH
BOSS

INLET
PRESSURE
PORT

ON

OFF

ON/OFF SWITCH
(Shown in ON position)

MAIN REGULATOR
ADJUSTMENT

OUTLET

OUTLET
PRESSURE
PORT

VENT PORT

A0226-001

Summary of Contents for TL8E

Page 1: ...ment closet alcove attic recreation room or garage and are also ideal for commercial applications All units are factory assembled wired and tested to assure safe dependable and economical installation...

Page 2: ...talling and servicing heating equipment can be hazardous due to the electrical components and the gas fired components Only trained and qualified personnel should install repair or service gas heating...

Page 3: ...spection by the carrier s agent should be made in writing Also before installation the unit should be checked for screws or bolts which may have loosened in transit There are no shipping or spacer bra...

Page 4: ...rizontal configuration then extra 2 minimum spacing may be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct...

Page 5: ...rt with required service accessibility HORIZONTAL APPLICATION ATTIC INSTALLATION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The...

Page 6: ...s must be level to ensure proper and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joist...

Page 7: ...minimum sizes listed in these instructions and in the codes The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace only use those approved gase...

Page 8: ...latest edition and all local codes The furnace shall be installed so that the electrical components are protected from water FIGURE 9 Gas Piping GROUND UNION DRIP LEG MANUAL SHUT OFF VALVE GROUND UNIO...

Page 9: ...set in the OFF position and the main electrical source disconnected connect the thermostat wiring from the wiring connections on the thermostat to the low voltage terminal block on the integrated furn...

Page 10: ...rmostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJH HDW DQ 5 9ROW RW LUVW 6WDJH HDW 9ROW RPPRQ 9ROW RPPRQ 5 9ROW RW 6HFRQG 6WDJH RPSUHVV...

Page 11: ...FURNACE IS NOT TO BE VENTED INTO AN UNLINED MASONRY CHIMNEY 2 This furnace must be vented into a fire clay tile lined masonry chim ney only if a source of dilution air is provided such as by common v...

Page 12: ...ind Such means shall not reduce the required free area of the air supply opening 7 An air supply inlet opening from the outdoors shall be located not less than 12 30 5 cm above the outside grade level...

Page 13: ...d that the ground union be loosened until the odor of gas is detected When gas is detected immediately retighten the union and check for leaks Allow five minutes for any gas to dissipate before contin...

Page 14: ...occur as follows a The induced draft blower will start and will run for several sec onds in order to bring fresh combustion air into the combustion chamber Then the induced draft blower will shut off...

Page 15: ...22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237...

Page 16: ...n gas valve 2 Turn gas and electrical supplies on and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw for the a...

Page 17: ...to 120 seconds The fan off setting must be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning th...

Page 18: ...alve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by 1 A dirty filter 2 If the indoor fan motor should fail 3 Too many supply...

Page 19: ...condition is not corrected the ignition control will lock out for 60 minutes During burner operation a momentary loss of power for 50 milliseconds or longer will de energize the gas valve When the pow...

Page 20: ...e if a temporary condition exists causing a furnace malfunction An example of this is a temporary interruption in gas supply that would prevent the furnace from lighting The control will keep trying t...

Page 21: ...FICE BURNER SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req d MOTOR MOUNT TUBING SILICON DIAGRAM WIRIN...

Page 22: ...5532522 UIM B 0619 22 Johnson Controls Ducted Systems SECTION XI WIRING DIAGRAM FIGURE 20 Wiring Diagram...

Page 23: ...stallation Instructions and Local Code Gas piping is connected including drip leg Supply plenum and return air are connected Filter Size Vent system is connected Thermostat wiring is complete Thermost...

Page 24: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Reviews: