background image

5532522-UIM-B-0619

12

Johnson Controls Ducted Systems

Combustion Air Source From Outdoors

The blocking effects of louvers, grilles and screens must be given con-
sideration in calculating free area. If the free area of a specific louver or
grille is not known, refer to Table 5, to estimate free area.

* Do not use less than 1/4” (6.4 mm) mesh

+ Free area of louvers and grille varies widely; the installer should follow 

louver or grille manufacturer’s instructions.

Dampers, Louvers and Grilles (Canada Only)

1. The free area of a supply air opening shall be calculated by sub-

tracting the blockage area of all fixed louvers grilles or screens from
the gross area of the opening.

2. Apertures in a fixed louver, a grille, or screen shall have no dimen-

sion smaller than 1/4” (6.4 mm).

3. A manually operated damper or manually adjustable louvers are

not permitted for use.

4. A automatically operated damper or automatically adjustable lou-

vers shall be interlocked so that the main burner cannot operate
unless either the damper or the louver is in the fully open position.

Air Supply Openings and Ducts

1. An opening may be used in lieu of a duct to provide the outside air

supply to an appliance unless otherwise permitted by the authority
having jurisdiction. The opening shall be located within 12” (30.5
cm) horizontally from, the burner level of the appliance. Refer to
“COMBUSTION AIR  SOURCE  FROM  OUTDOORS  and  VENT
AND SUPPLY AIR SAFETY CHECK” in these instructions for addi-
tional information and safety check procedure.

2. The duct shall be either metal, or a material meeting the class 1

requirements of CAN4-S110 Standard for Air Ducts.

3. The duct shall be least the same cross-sectional area as the free

area of the air supply inlet opening to which it connects. 

4. The duct shall terminate within 12” (30.5 cm) above, and within 24”

(61 cm) horizontally from, the burner level of the appliance having
the largest input.

5. A square or rectangular shaped duct shall only be used when the

required free area of the supply opening is 9 in

2

 (58.06 cm

2

) or

larger. When a square or rectangular duct is used, its small dimen-
sion shall not be less than 3” (7.6 cm).

6. An air inlet supply from outdoors shall be equipped with a means to

prevent the direct entry of rain and wind. Such means shall not
reduce the required free area of the air supply opening. 

7. An air supply inlet opening from the outdoors shall be located not

less than 12” (30.5 cm) above the outside grade level.

Combustion Air Source from Outdoors

1. Two permanent openings, one within 12” (30.5 mm) of the top and

one within 12” (30.5 mm) of the bottom of the confined space, shall
communicate directly or by means of ducts with the outdoors, crawl
spaces or attic spaces.

2. One permanent opening, commencing within 12” (30.5 cm) of the

top of the enclosure, shall be permitted where the equipment has
clearances of at least 1” (2.54 cm) from the sides and back and 6”
(15.24 cm) from the front of the appliance. The opening shall com-
municate directly with the outdoors and shall have a minimum free
area of:

a. 1 square in per 3000 Btu per hour (6.45 cm

3

 per 0.879 kW) of the

total input rating of all equipment located in the enclosure.

b. Not less than the sum of all vent connectors in the confined

space.

Table 5: 

Estimated Free Area

Wood or Metal

Louvers or Grilles

Wood 20-25%*

Metal 60-70% *

1/4” (0.635 cm)

mesh or larger 100%

 WARNING

When a Category I furnace is removed or replaced, the original vent-
ing system may no longer be correctly sized to properly vent the
attached appliances.
An improperly sized vent system can cause CARBON MONOXIDE to
spill into the living space causing personal injury, and or death.

Table 6: 

Unconfined Space Minimum Area

BTUH Input Rating

Minimum Free Area

Required for Each Opening

60,000

60 in

2

 (387 cm

2

)

80,000

80 in

2

 (516 cm

2

)

100,000

100 in

2

 (645 cm

2

)

Table 7: 

Free Area

BTUH Input 

Rating

Minimum Free Area Required for Each Opening

Horizontal Duct 

(2,000 BTUH)

Vertical Duct or 

Opening to Outside 

(4,000 BTUH)

Round Duct

(4,000 BTUH)

60,000

30 in

2

 (193 cm

2

)

15 in

2

 (97 cm

2

)

5” (13 cm)

80,000

40 in

2

 (258 cm

2

)

20 in

2

 (129 cm

2

)

5” (13 cm)

100,000

50 in

2

 (322 cm

2

)

25 in

2

 (161 cm

2

)

6” (15 cm)

EXAMPLE: Determining Free Area.
Appliance 1 

Appliance 

Total 

Input

100,000  + 30,000 = (130,000 

 4,000) = 32.5 Sq. In. Vertical

Appliance 1 

Appliance 

Total 

Input

100,000  + 30,000 = (130,000 

 2,000) = 65 Sq. In. Horizontal

!

 FIGURE 16: 

Outside and Ambient Combustion Air

*DEOH
9HQW

*DV
9HQW

6RIILW
9HQW

9HQWLODWHG

$WWLF

7RS$ERYH
,QVXODWLRQ

2SWLRQDO
,QOHWD

2XWOHW
$LUD

9HQWLODWHG

&UDZO6SDFH

*DV
:DWHU
+HDWHU

)XUQDFH

6RIILW
9HQW

*DV
:DWHU
+HDWHU

,QOHW
$LUD

,QOHW
$LUE

)XUQDFH

*DV
9HQW

2XWOHW
$LUD

2XWOHW
$LUE

,QOHW
$LUD

,QOHW
$LUE

*DV
:DWHU
+HDWHU

)XUQDFH

9HQWLODWHG

$WWLF

7RS$ERYH
,QVXODWLRQ

*DEOH
9HQW

*DV
9HQW

$

Summary of Contents for TL8E

Page 1: ...ment closet alcove attic recreation room or garage and are also ideal for commercial applications All units are factory assembled wired and tested to assure safe dependable and economical installation...

Page 2: ...talling and servicing heating equipment can be hazardous due to the electrical components and the gas fired components Only trained and qualified personnel should install repair or service gas heating...

Page 3: ...spection by the carrier s agent should be made in writing Also before installation the unit should be checked for screws or bolts which may have loosened in transit There are no shipping or spacer bra...

Page 4: ...rizontal configuration then extra 2 minimum spacing may be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct...

Page 5: ...rt with required service accessibility HORIZONTAL APPLICATION ATTIC INSTALLATION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The...

Page 6: ...s must be level to ensure proper and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joist...

Page 7: ...minimum sizes listed in these instructions and in the codes The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace only use those approved gase...

Page 8: ...latest edition and all local codes The furnace shall be installed so that the electrical components are protected from water FIGURE 9 Gas Piping GROUND UNION DRIP LEG MANUAL SHUT OFF VALVE GROUND UNIO...

Page 9: ...set in the OFF position and the main electrical source disconnected connect the thermostat wiring from the wiring connections on the thermostat to the low voltage terminal block on the integrated furn...

Page 10: ...rmostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJH HDW DQ 5 9ROW RW LUVW 6WDJH HDW 9ROW RPPRQ 9ROW RPPRQ 5 9ROW RW 6HFRQG 6WDJH RPSUHVV...

Page 11: ...FURNACE IS NOT TO BE VENTED INTO AN UNLINED MASONRY CHIMNEY 2 This furnace must be vented into a fire clay tile lined masonry chim ney only if a source of dilution air is provided such as by common v...

Page 12: ...ind Such means shall not reduce the required free area of the air supply opening 7 An air supply inlet opening from the outdoors shall be located not less than 12 30 5 cm above the outside grade level...

Page 13: ...d that the ground union be loosened until the odor of gas is detected When gas is detected immediately retighten the union and check for leaks Allow five minutes for any gas to dissipate before contin...

Page 14: ...occur as follows a The induced draft blower will start and will run for several sec onds in order to bring fresh combustion air into the combustion chamber Then the induced draft blower will shut off...

Page 15: ...22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237...

Page 16: ...n gas valve 2 Turn gas and electrical supplies on and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw for the a...

Page 17: ...to 120 seconds The fan off setting must be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning th...

Page 18: ...alve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by 1 A dirty filter 2 If the indoor fan motor should fail 3 Too many supply...

Page 19: ...condition is not corrected the ignition control will lock out for 60 minutes During burner operation a momentary loss of power for 50 milliseconds or longer will de energize the gas valve When the pow...

Page 20: ...e if a temporary condition exists causing a furnace malfunction An example of this is a temporary interruption in gas supply that would prevent the furnace from lighting The control will keep trying t...

Page 21: ...FICE BURNER SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req d MOTOR MOUNT TUBING SILICON DIAGRAM WIRIN...

Page 22: ...5532522 UIM B 0619 22 Johnson Controls Ducted Systems SECTION XI WIRING DIAGRAM FIGURE 20 Wiring Diagram...

Page 23: ...stallation Instructions and Local Code Gas piping is connected including drip leg Supply plenum and return air are connected Filter Size Vent system is connected Thermostat wiring is complete Thermost...

Page 24: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Reviews: