Johnson Controls Ducted Systems

13

3. The duct shall be least the same cross-sectional area as the free

area of the air supply inlet opening to which it connects.

4. The blocking effects of louvers, grilles and screens must be given

consideration in calculating free area. If the free area of a specific
louver or grille is not known. Refer to Table 5 to estimate free area.

Ventilated Combustion Air

The ventilated attic space or a crawl space from which the combustion 
air is taken must comply with the requirements specified in “AIR 
SOURCE FROM OUTDOORS” in this instruction or in Section 5.3, Air 
for Combustion and Ventilation of the National Fuel Gas Code, ANSI 
Z223.1 (latest edition). This type installation requires two properly sized 
pipes. One brings combustion air from a properly ventilated attic space 
or crawl space and a second pipe that extends from the furnace vent 
connection (top right of unit) to the exterior of the building. 

Vent and Supply (Outside) Air Safety Check Procedure

For Category I furnaces, vent installations shall be in accordance with
Parts 7 and 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
and or Section 7 and Appendix B of the CSA B149.1, Natural Gas and
Propane Installation Codes, the local building codes, furnace and vent
manufacturer's instructions.
Multi-story or common venting systems are permitted and must be
installed in accordance with the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 and / or the CSA B149.1, Natural Gas and Propane Installa-
tion Codes, local codes, and the manufacturer's instructions.
Vent connectors serving Category I furnaces shall not be connected
into any portion of mechanical draft systems operating under positive
pressure.
Horizontal portions of the venting system shall be supported to prevent
sagging using hangers or perforated straps and must slope upwards
not less than 1/4” per foot (21 mm/m) from the furnace to the vent termi-
nal.
It is recommended that you follow the venting safety procedure below.
This procedure is designed to detect an inadequate ventilation system
that can cause the appliances in the area to operate improperly causing
unsafe levels of Carbon Monoxide or an unsafe condition to occur.

SECTION VII: START-UP AND 

ADJUSTMENTS

The following start-up checks 

MUST

 be performed by the furnace

installer on every new furnace installation. 
1. Gas piping leak check
2. Ignition check
3. Furnace input rate check
4. Air temperature rise check 
Instructions on how to perform each of these required installation
checks are listed in the sections below. 

When the gas supply is initially connected to the furnace, the gas piping
may be full of air. In order to purge this air, it is recommended that the
ground union be loosened until the odor of gas is detected. When gas is
detected, immediately retighten the union and check for leaks. Allow
five minutes for any gas to dissipate before continuing with the start-up
procedure. Be sure proper ventilation is available to dilute and carry
away any vented gas.

 WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation could result in carbon-
monxide poisoning or death.
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances
connected to the venting system are not in operation:

1. Inspect the venting system for proper size and horizontal pitch. Determine that there is no blockage, restriction, leakage, corrosion or other defi-

ciencies, which could cause an unsafe condition

2. Close all building doors and windows.
3. Turn on clothes dryers and TURN ON any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum

speed. Open the fireplace dampers. Do not operate a summer exhaust fan.

4. Follow the lighting instructions. Place the appliance being inspected in operation. Adjust thermostat so the appliance shall operate continu-

ously.

5. Test each appliance (such as a water heater) equipped with a draft hood for spillage (down-draft or no draft) at the draft hood relief opening

after 5 minutes of main burner operation. Appliances that do not have draft hoods need to be checked at the vent pipe as close to the appliance
as possible. Use a combustion analyzer to check the CO

2

 and CO levels of each appliance. Use a draft gauge to check for a downdraft or inad-

equate draft condition.

6. After it has been determined that each appliance properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace

dampers and any other gas burning appliance to their normal condition.

7. If improper venting is observed during any of the above tests, a problem exists with either the venting system or the appliance does not have

enough combustion air (Supply Air from outside) to complete combustion. This condition must be corrected before the appliance can function
safely.

NOTE: 

An unsafe condition exists when the CO reading exceeds 40 ppm and the draft reading is not in excess of - 0.1” w.c. (-25 kPa) with all

of the appliance(s) operating at the same time.

8. Any corrections to the venting system and / or to the supply (outside) air system must be in accordance with the National Fuel Gas Code

Z223.1 or CAN/CGA B149.1 Natural Gas and Propane Installation Code (latest editions). If the vent system must be resized, follow the appro-
priate tables in Appendix G of the above codes or for this appliance.

!

IMPORTANT:  

All electrical connections made in the field and in the

factory should be checked for proper tightness.

Summary of Contents for TL8E

Page 1: ...ment closet alcove attic recreation room or garage and are also ideal for commercial applications All units are factory assembled wired and tested to assure safe dependable and economical installation...

Page 2: ...talling and servicing heating equipment can be hazardous due to the electrical components and the gas fired components Only trained and qualified personnel should install repair or service gas heating...

Page 3: ...spection by the carrier s agent should be made in writing Also before installation the unit should be checked for screws or bolts which may have loosened in transit There are no shipping or spacer bra...

Page 4: ...rizontal configuration then extra 2 minimum spacing may be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct...

Page 5: ...rt with required service accessibility HORIZONTAL APPLICATION ATTIC INSTALLATION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The...

Page 6: ...s must be level to ensure proper and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joist...

Page 7: ...minimum sizes listed in these instructions and in the codes The furnace rating plate and the instructions in this section specify the type of gas approved for this furnace only use those approved gase...

Page 8: ...latest edition and all local codes The furnace shall be installed so that the electrical components are protected from water FIGURE 9 Gas Piping GROUND UNION DRIP LEG MANUAL SHUT OFF VALVE GROUND UNIO...

Page 9: ...set in the OFF position and the main electrical source disconnected connect the thermostat wiring from the wiring connections on the thermostat to the low voltage terminal block on the integrated furn...

Page 10: ...rmostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJH HDW DQ 5 9ROW RW LUVW 6WDJH HDW 9ROW RPPRQ 9ROW RPPRQ 5 9ROW RW 6HFRQG 6WDJH RPSUHVV...

Page 11: ...FURNACE IS NOT TO BE VENTED INTO AN UNLINED MASONRY CHIMNEY 2 This furnace must be vented into a fire clay tile lined masonry chim ney only if a source of dilution air is provided such as by common v...

Page 12: ...ind Such means shall not reduce the required free area of the air supply opening 7 An air supply inlet opening from the outdoors shall be located not less than 12 30 5 cm above the outside grade level...

Page 13: ...d that the ground union be loosened until the odor of gas is detected When gas is detected immediately retighten the union and check for leaks Allow five minutes for any gas to dissipate before contin...

Page 14: ...occur as follows a The induced draft blower will start and will run for several sec onds in order to bring fresh combustion air into the combustion chamber Then the induced draft blower will shut off...

Page 15: ...22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237...

Page 16: ...n gas valve 2 Turn gas and electrical supplies on and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw for the a...

Page 17: ...to 120 seconds The fan off setting must be long enough to adequately cool the furnace but not so long that cold air is blown into the heated space The fan off timing may be adjusted by positioning th...

Page 18: ...alve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by 1 A dirty filter 2 If the indoor fan motor should fail 3 Too many supply...

Page 19: ...condition is not corrected the ignition control will lock out for 60 minutes During burner operation a momentary loss of power for 50 milliseconds or longer will de energize the gas valve When the pow...

Page 20: ...e if a temporary condition exists causing a furnace malfunction An example of this is a temporary interruption in gas supply that would prevent the furnace from lighting The control will keep trying t...

Page 21: ...FICE BURNER SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req d MOTOR MOUNT TUBING SILICON DIAGRAM WIRIN...

Page 22: ...5532522 UIM B 0619 22 Johnson Controls Ducted Systems SECTION XI WIRING DIAGRAM FIGURE 20 Wiring Diagram...

Page 23: ...stallation Instructions and Local Code Gas piping is connected including drip leg Supply plenum and return air are connected Filter Size Vent system is connected Thermostat wiring is complete Thermost...

Page 24: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Reviews: