background image

5894307-UIM-B-0920

Johnson Controls Ducted Systems

15

SECTION VII: COMBUSTION AIR AND 

VENT SYSTEM

COMBUSTION AIR AND VENT SAFETY

This Category IV, dual certified direct vent furnace is designed for resi-
dential application. It can be installed without modification to the con-
densate system in a basement, garage, equipment room, alcove, attic
or any other indoor location where all required clearance to combusti-
bles and other restrictions are met. The combustion air and the venting
system must be installed in accordance with Section 5.3, Air for Com-
bustion and Ventilation, of the National Fuel Gas Code Z223.1/NFPA 54
(latest edition) or Sections 7.2, 7.3, or 7.4 of CSA B149.1, National Gas
and Propane Codes (latest edition), or applicable provisions of the local
building code, and these instructions.

COMBUSTION AIR/VENT PIPE SIZING

The size of pipe required is determined by the furnace model, the total
length of pipe required, and the number of elbows required.
Table  5  lists  the  maximum  equivalent  length  of  pipe  allowed  for  each
model of furnace. The equivalent length of pipe for each elbow installed
is listed in Table 7. 

Note: 

The  equivalent  length  of  the  vent  system  is  the  total  length  of

straight pipe plus the equivalent length of all of the elbows.
Adhere to the following rules:

• Drain, waste, and vent (DWV) elbows with a long radius (sweep)

are  recommended.  Standard  DWV  elbows  can  be  used,  but
because  they  have  a  longer  equivalent  length,  they  reduce  the
total length of pipe that is allowed. Short radius (plumbing or pres-
sure)  elbows  are  not  allowed  for  venting.  The  standard  dimen-
sions of the acceptable elbows are shown in Figure 18.

• The maximum equivalent length listed in Table 5 is for the vent

piping  and  the  air  intake  piping  separately.  For  example,  if  the
table allows 65 equivalent ft for a particular model, the vent can
have 65 equivalent ft of pipe, and the combustion air intake can
have another 65 equivalent ft of pipe.

• Three vent terminal elbows (two for the vent and one for the com-

bustion air intake) are already accounted for and do not need to
be included in the equivalent length calculation.

• All  PVC  or ABS  combustion  air  and  vent  pipe  must  conform  to

American National Standards Institute (ANSI) and American Soci-
ety for Testing and Materials (ASTM) standards D1785 (Schedule
40  PVC),  D2665  (PVC-DWV),  F891  (PVC-DWV  Cellular  Core),
D2261  (ABS-DWV)  or  F628  (Schedule  40  ABS).  Pipe  cement
and  primer  must  conform  to  ASTM  Standard  D2546  (PVC)  or
D2235 (ABS). If ABS pipe is used, any joint where ABS pipe is
joined to PVC pipe must be glued with cement that is approved
for use with BOTH materials. Metallic materials must not be used
for venting or air intake.

• If a flexible connector is used in the vent system, it must be made

of  a  material  that  is  resistant  to  acidic  exposure  and  to  at  least
225°F (107°C) temperature. Flexible connectors are also allowed
in the combustion air pipe. 

• All  models  are  supplied  with  2  in.  (5.1  cm)  vent  connections.

When the pipe must be increased to 3 in. (7.6 cm) diameter, the
transition from 2 in. to 3 in. must be done as close to the furnace
as  possible. The  2  in.  to  3  in.  increase  must  be  installed  in  the
vertical position to avoid creating an area that pools water.

• In  Canada,  vents  must  be  certified  to  ULC  S636,  Standard  for

Type BH Gas Venting Systems.

• In  Canada,  the  first  3  ft  (91.4  cm)  of  the  vent  must  be  readily

accessible for inspection.

• For single-pipe systems, it is best practice to install the combus-

tion air coupling provided and install approximately 18 in. (46 cm)
of PVC pipe on the furnace.

• The minimum vent length for all models is 5 ft (1.5 m).

POLYPROPYLENE VENT/INTAKE PIPING

The  ULC  S636  approved  polypropylene  (PP)  vent  piping  materials
listed below have been tested and approved for use with this furnace.
DO NOT mix parts made by different manufacturers. The entire vent/air
intake system must be made from pipe, fittings, and termination made
by the same manufacturer. Only single-wall rigid polypropylene pipe is
approved for these furnaces. Use of flexible polypropylene pipe is not
allowed.

Selkirk Polyflue (Hart &Cooley) part numbers

• Horizontal concentric termination - 2 in. - 2PF-HCT
• Horizontal concentric termination - 3 in. - 3PF-HCT
• Locking band - PF-LB

Consult  the  Polyflue  installation  instructions  for  assembly  details.  For
other Polyflue pipe and fitting part numbers, visit 

www.polyflue.com

.

Duravent Polypro part numbers

• Adapter to air intake coupling - 2PPS-ADL
• Adapter connector - PPS-PAC
• Twin pipe horizontal termination - 2 in. - 2PPS-HTPL
• Twin pipe horizontal termination - 3 in. - 3PPS-HTPL

Consult  the  Polypro  installation  instructions  for  assembly  details.  For
other Polypro pipe and fitting part numbers, visit 

www.duravent.com

.

Centrotherm Innoflue part numbers

• Adapter to air intake coupling - ISAGL0202
• Adapter to draft inducer blower - ISAAL0202
• Low profile wall termination - 2 in. - ISLPT0202
• Low profile wall termination - 3 in. - ISLPT0303

Consult  the  Innoflue  installation  instructions  for  assembly  details.
For  other  Innoflue  pipe  and  fitting  part  numbers,  visit

www.centrotherm.us.com

.

IMPORTANT:  

The  vent  system  must  be  installed  as  specified  in

these instructions for residential and non-HUD modular homes. The
direct vent system is the only configuration that can be installed in a
non-HUD modular home.

 WARNING

This  furnace  may  not  be  common  vented  with  any  other  appliance,
since  it  requires  separate,  properly  sized  air  intake  and  vent  lines.
The furnace shall not be connected to any type of B, BW, or L vent or
vent connector, and not connected to any portion of a factory-built or
masonry chimney.
The furnace shall not be connected to a chimney flue serving a sepa-
rate appliance designed to burn solid fuel.

 CAUTION

When combustion air pipe is installed above a suspended ceiling or
when it passes through a warm and humid space, the pipe may need
insulated if 2 ft or more of pipe is exposed.
Vent piping must be insulated if it will be subjected to freezing tem-
peratures  such  as  routing  through  unheated  areas  or  through  an
unused chimney.

!

!

Summary of Contents for TL9E Series

Page 1: ...Wiring Diagram 32 LIST OF TABLES Unit Clearances to Combustibles 4 Cabinet and Duct Dimensions 6 Recommended Filter Sizes High Velocity 600 FPM 7 Ratings and Physical Electrical Data 8 Maximum Equival...

Page 2: ...alled directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical characteristics match All models use nom...

Page 3: ...t piping and elbows are required As centralized with the air distribution as possible Where adequate combustion air is available particularly when the appliance is not using outdoor combustion air Whe...

Page 4: ...be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct such that smoke or reflected light would be observable...

Page 5: ...ION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The line contact is only permissible between lines that are formed by the inters...

Page 6: ...t and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists See Figure 5 for details and...

Page 7: ...p leg and ground union is required See Figure 10 For left side supply gas pipe arrangement two 1 2 in elbows and two 1 2 in x 1 1 2 in pipe nipples must be used The arrangement shown in Figure 9 align...

Page 8: ...with DOE test procedures Wire size and overcurrent protection must comply with the National Electrical Code NFPA 70 latest edition and all local codes The furnace must be installed so the electrical...

Page 9: ...Figure 11 LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the m...

Page 10: ...1 67 LU RQGLWLRQHU 9ROW RPPRQ RPSUHVVRU RQWDFWRU XOO 6WDJH HDW 7 50267 7 Figure 13 Thermostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJ...

Page 11: ...pplied to the hose con nected to the top of the condensate trap Screw the condensate trap to the condensate trap bracket supplied Then thread the hose adapters together below the furnace casing using...

Page 12: ...collec tor box as shown in Figures 16 and 17 The drain hose must not sag or droop after it is installed If glue is used when connecting the intake pipe to the intake coupling the drain opening in the...

Page 13: ...5894307 UIM B 0920 Johnson Controls Ducted Systems 13 Figure 16 Upflow Configuration UPFLOW LEFT SIDE DRAIN UPFLOW RIGHT SIDE DRAIN EXTERNAL CONDENSATE TRAP EXTERNAL CONDENSATE TRAP A1128 001...

Page 14: ...DRAIN AIRFLOW EXTERNAL CONDENSATE TRAP HORIZONTAL LEFT HORIZONTAL RIGHT MOVE RAIN GUTTER HOSE TO THIS POSITION MOVE CONDENSATE DRAIN HOSE TO THIS POSITION INTAKE PIPE DRAIN AIRFLOW EXTERNAL CONDENSAT...

Page 15: ...models are supplied with 2 in 5 1 cm vent connections When the pipe must be increased to 3 in 7 6 cm diameter the transition from 2 in to 3 in must be done as close to the furnace as possible The 2 i...

Page 16: ...igure 18 Elbow Dimensions A A A A STANDARD ELBOW LONG SWEEP ELBOW Table 6 Elbow Dimensions Elbow A Dimension Illustrated in Figure 18 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 i...

Page 17: ...nform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal 8 Install the combustion air and vent piping such that it has a 1 4 in ft 21...

Page 18: ...equirements of the gas supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with...

Page 19: ...3 to 24 Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 23 and 24 can...

Page 20: ...tion See Figure 28 VENTILATED COMBUSTION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated att...

Page 21: ...operated damper or manually adjustable louvers are not permitted for use An automatically operated damper or automatically adjustable louvers must be interlocked so the main burner can not operate un...

Page 22: ...kW of the total input rating of all equipment located in the enclosure Not less than the sum of all vent connectors in the confined space The duct must be least the same cross sectional area as the fr...

Page 23: ...s dryers and TURN ON any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Open the fireplace dampers Do not operate a summer exhaust fan 4 Follow the light...

Page 24: ...surface igniter glows for about 17 s b After this warm up the induced draft blower starts again and the ignition module opens the main gas valve c After flame is established the supply air blower sta...

Page 25: ...0 300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 23...

Page 26: ...ws on main gas valve 2 Turn on gas and electrical supplies and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw...

Page 27: ...gas sample for analysis it is permissi ble to drill a small hole in the plastic flue pipe for a sample probe pro vided that the vent piping is PVC and the hole is correctly sealed afterwards If using...

Page 28: ...ated on the furnace vesti bule panel near the gas valve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by the following A dirty...

Page 29: ...sensed within 1 0 s The gas valve de energizes and the control begins a recycle operation A normal ignition sequence begins after a 15 s inter purge If during the five recycles the gas supply does not...

Page 30: ...d Red Flashes Indicates incorrect line voltage polarity The polar ity of the incoming power to the furnace is reversed Soft Lockout The control includes a soft lockout that resets automati cally after...

Page 31: ...Door 1 5 ft required GROMMET 3 required HARNESS WIRING HOSE CONDENSATE HOSE RAIN GUTTER KNOB QUARTER TURN 4 required MOTOR MOUNT ORIFICE BURNER PAN CONDENSATE PLUG SEAL 7 8 in PLUG SEAL 2 3 8 in PLUG...

Page 32: ...5894307 UIM B 0920 32 Johnson Controls Ducted Systems SECTION XII WIRING DIAGRAM Figure 33 Wiring Diagram...

Page 33: ...ree Ells of 90 Degree Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control b...

Page 34: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Reviews: