background image

5894307-UIM-B-0920

Johnson Controls Ducted Systems

27

ADJUSTMENT OF TEMPERATURE RISE

After about 5 min of operation, determine the furnace temperature rise.
Take  readings  of  both  the  return  air  and  the  heated  air  in  the  ducts
about  6  ft  (1.83  m)  from  the  furnace,  where  they  are  not  affected  by
radiant  heat.  Increase  the  blower  speed  to  decrease  the  temperature
rise. Decrease the blower speed to increase the rise.
This furnace has a standard ECM motor. The blower motor speed taps
are  located  on  the  furnace  control  board  in  the  blower  compartment.
See Figure 32 and refer to the unit wiring label to change the  blower
speed. Place all unused motor leads on the PARK terminals. Two PARK
terminals are provided. To use the same speed tap for heating and cool-
ing,  the  terminals  must  be  jumpered  together.  This  control  changes
blower  speeds  based  on  other  24-V  thermostat  inputs  (Y,  W)  respec-
tively.

ADJUSTMENT OF FAN CONTROL SETTINGS

This furnace is equipped with a time-on/time-off heating fan control. The
fan  on  delay  is  fixed  at  30  s.  The  fan  off  delay  has  four  settings
(A = 60 s, B = 90 s, C = 120 s, and D = 180 s). The fan off delay is fac-
tory set to 120 s. The fan-off setting must be long enough to adequately
cool the furnace, but not so long that cold air is blown into the heated
space. The fan-off timing can be adjusted by positioning the jumper on
two of the four pins as shown in Figure 32.
The furnace is also equipped with a cooling fan on time delay. The cool-
ing fan on delay has two settings (A = 6 s, B = 24 s). The cooling fan on
delay can be adjusted by positioning the COOL jumper as shown in Fig-
ure 32.

TAKING A FLUE GAS SAMPLE

If it is necessary to obtain a flue gas sample for analysis, it is permissi-
ble to drill a small hole in the plastic flue pipe for a sample probe, pro-
vided  that  the  vent  piping  is  PVC  and  the  hole  is  correctly  sealed
afterwards.  If  using  a  polypropylene  vent  system,  the  vent  system’s
manufacturer  test  port  fitting  must  be  used. 

DO  NOT

  drill  a  test  port

hole in polypropylene piping. Use the following procedure:
1. Drill an 11/32 in. hole in the side wall of the PVC vent pipe. If the

hole is in a horizontal section of the vent pipe, make sure that it is
located away from the bottom where condensation may be flowing
back toward the furnace.

2. Operate the furnace for a minimum of 10 min to ensure stable oper-

ation of the combustion process. 

3. Sample the flue gas as necessary to obtain CO readings.
4. Using a 1/8 in. pipe tap, cut threads into the sampling hole of the

PVC pipe.

5. Use high temp RTV as a sealant on the threads of a 1/8 in. brass

MPT plug and insert it three turns into the hole to correctly seal it.

 DANGER

The  temperature  rise,  or  temperature  difference  between  the  return
air and the supply (heated) air from the furnace, must be within the
range  shown  on  the  furnace  rating  plate  and  within  the  application
limitations shown in Table 4.
The  supply  air  temperature  cannot  exceed  the 

“Maximum  Supply

Air Temperature”

 specified in these instructions and on the furnace

rating plate. Under NO circumstances can the furnace be allowed to
operate above the Maximum Supply Air Temperature. Operating the
furnace above the Maximum Supply Air Temperature will cause pre-
mature heat exchanger failure, high levels of Carbon Monoxide, a fire
hazard, personal injury, property damage, and/or death.

!

 Figure 32: 

Furnace Control Board

DIAGNOSTIC
ERROR CODE
BUTTON

COOL BLOWER
ON JUMPER

HEAT BLOWER
OFF JUMPER

HUMIDIFIER
TERMINAL 

ELECTRONIC AIR CLEANER
TERMINAL

3 AMP
FUSE

DIAGNOSTIC
LED

ID PLUG

A1104-001

Summary of Contents for TL9E Series

Page 1: ...Wiring Diagram 32 LIST OF TABLES Unit Clearances to Combustibles 4 Cabinet and Duct Dimensions 6 Recommended Filter Sizes High Velocity 600 FPM 7 Ratings and Physical Electrical Data 8 Maximum Equival...

Page 2: ...alled directly on carpeting tile or other combustible material other than wood flooring Check the rating plate and power supply to be sure that the elec trical characteristics match All models use nom...

Page 3: ...t piping and elbows are required As centralized with the air distribution as possible Where adequate combustion air is available particularly when the appliance is not using outdoor combustion air Whe...

Page 4: ...be needed to ensure against drain pan distortion On all installations without a coil a removable access panel is recom mended in the outlet duct such that smoke or reflected light would be observable...

Page 5: ...ION This appliance is certified for line contact when the furnace is installed in the horizontal left or right position The line contact is only permissible between lines that are formed by the inters...

Page 6: ...t and quiet fur nace operation When suspending the furnace use a secure platform constructed of plywood or other building materials secured to the floor or ceiling joists See Figure 5 for details and...

Page 7: ...p leg and ground union is required See Figure 10 For left side supply gas pipe arrangement two 1 2 in elbows and two 1 2 in x 1 1 2 in pipe nipples must be used The arrangement shown in Figure 9 align...

Page 8: ...with DOE test procedures Wire size and overcurrent protection must comply with the National Electrical Code NFPA 70 latest edition and all local codes The furnace must be installed so the electrical...

Page 9: ...Figure 11 LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermostat set in the OFF position and the m...

Page 10: ...1 67 LU RQGLWLRQHU 9ROW RPPRQ RPSUHVVRU RQWDFWRU XOO 6WDJH HDW 7 50267 7 Figure 13 Thermostat Chart Single Stage HP with Single Stage Furnaces 6LQJOH 6WDJH R1R XUQDFH 6LQJOH 6WDJH HDW 3XPS 6HFRQG 6WDJ...

Page 11: ...pplied to the hose con nected to the top of the condensate trap Screw the condensate trap to the condensate trap bracket supplied Then thread the hose adapters together below the furnace casing using...

Page 12: ...collec tor box as shown in Figures 16 and 17 The drain hose must not sag or droop after it is installed If glue is used when connecting the intake pipe to the intake coupling the drain opening in the...

Page 13: ...5894307 UIM B 0920 Johnson Controls Ducted Systems 13 Figure 16 Upflow Configuration UPFLOW LEFT SIDE DRAIN UPFLOW RIGHT SIDE DRAIN EXTERNAL CONDENSATE TRAP EXTERNAL CONDENSATE TRAP A1128 001...

Page 14: ...DRAIN AIRFLOW EXTERNAL CONDENSATE TRAP HORIZONTAL LEFT HORIZONTAL RIGHT MOVE RAIN GUTTER HOSE TO THIS POSITION MOVE CONDENSATE DRAIN HOSE TO THIS POSITION INTAKE PIPE DRAIN AIRFLOW EXTERNAL CONDENSAT...

Page 15: ...models are supplied with 2 in 5 1 cm vent connections When the pipe must be increased to 3 in 7 6 cm diameter the transition from 2 in to 3 in must be done as close to the furnace as possible The 2 i...

Page 16: ...igure 18 Elbow Dimensions A A A A STANDARD ELBOW LONG SWEEP ELBOW Table 6 Elbow Dimensions Elbow A Dimension Illustrated in Figure 18 2 in Standard 2 5 16 in 3 in Standard 3 1 16 in 2 in Sweep 3 1 4 i...

Page 17: ...nform to ASTM D2564 for PVC or ASTM D2235 for ABS piping 7 All joints must provide a permanent airtight and watertight seal 8 Install the combustion air and vent piping such that it has a 1 4 in ft 21...

Page 18: ...equirements of the gas supplier 12 in 30 5 cm or in accordance with local installation codes and the requirements of the gas supplier F Clearance to outside corner 12 in 30 5 cm or in accordance with...

Page 19: ...3 to 24 Each furnace must have a separate vent pipe Under NO circumstances can the two vent pipes be tied together The combustion air side of the two pipe configuration shown in Figures 23 and 24 can...

Page 20: ...tion See Figure 28 VENTILATED COMBUSTION AIR Combustion air is supplied through a PVC or ABS pipe that is connected to the PVC coupling attached to the burner box and is terminated in a ventilated att...

Page 21: ...operated damper or manually adjustable louvers are not permitted for use An automatically operated damper or automatically adjustable louvers must be interlocked so the main burner can not operate un...

Page 22: ...kW of the total input rating of all equipment located in the enclosure Not less than the sum of all vent connectors in the confined space The duct must be least the same cross sectional area as the fr...

Page 23: ...s dryers and TURN ON any exhaust fans such as range hoods and bathroom exhausts so they shall operate at maximum speed Open the fireplace dampers Do not operate a summer exhaust fan 4 Follow the light...

Page 24: ...surface igniter glows for about 17 s b After this warm up the induced draft blower starts again and the ignition module opens the main gas valve c After flame is established the supply air blower sta...

Page 25: ...0 300 750 78 46 92 231 25 144 288 720 80 45 90 225 26 138 277 692 82 44 88 220 27 133 267 667 84 43 86 214 28 129 257 643 86 42 84 209 29 124 248 621 88 41 82 205 30 120 240 600 90 40 80 200 31 116 23...

Page 26: ...ws on main gas valve 2 Turn on gas and electrical supplies and follow the operating instruc tions to place the unit back in operation 3 Adjust manifold pressure by adjusting gas valve regulator screw...

Page 27: ...gas sample for analysis it is permissi ble to drill a small hole in the plastic flue pipe for a sample probe pro vided that the vent piping is PVC and the hole is correctly sealed afterwards If using...

Page 28: ...ated on the furnace vesti bule panel near the gas valve This is an automatic reset control that provides over temperature protection due to reduced airflow This may be caused by the following A dirty...

Page 29: ...sensed within 1 0 s The gas valve de energizes and the control begins a recycle operation A normal ignition sequence begins after a 15 s inter purge If during the five recycles the gas supply does not...

Page 30: ...d Red Flashes Indicates incorrect line voltage polarity The polar ity of the incoming power to the furnace is reversed Soft Lockout The control includes a soft lockout that resets automati cally after...

Page 31: ...Door 1 5 ft required GROMMET 3 required HARNESS WIRING HOSE CONDENSATE HOSE RAIN GUTTER KNOB QUARTER TURN 4 required MOTOR MOUNT ORIFICE BURNER PAN CONDENSATE PLUG SEAL 7 8 in PLUG SEAL 2 3 8 in PLUG...

Page 32: ...5894307 UIM B 0920 32 Johnson Controls Ducted Systems SECTION XII WIRING DIAGRAM Figure 33 Wiring Diagram...

Page 33: ...ree Ells of 90 Degree Ells Polarity is correct black is L1 hot white is N neutral Ground wire is connected Line voltage value to furnace volts AC Low voltage value between R and C on furnace control b...

Page 34: ...ure in w c Return Static in w c after Air Side Heating Air Side Cooling Air Side Continuous Fan Clean Up Give owner the owner s manual provided Explain thermostat use and programming if applicable to...

Reviews: