background image

5402847-UIM-A-0917

Johnson Controls Unitary Products

3

COMBUSTION AIR QUALITY 

(LIST OF CONTAMINANTS)

The furnace requires 

OUTDOOR AIR

 for combustion when the furnace

is located in any of the following environments.

Restricted Environments 

Commercial buildings 

Buildings with indoor pools 

Furnaces installed in laundry rooms 

Furnaces installed in hobby or craft rooms 

Furnaces installed near chemical storage areas 

Chemical exposure 

The furnace requires 

OUTDOOR AIR

 for combustion when the furnace

is located in an area where the furnace is being exposed to the follow-
ing substances and / or chemicals.

Permanent wave solutions 

Chlorinated waxes and cleaners 

Chlorine based swimming pool chemicals 

Water softening chemicals 

De-icing salts or chemicals 

Carbon tetrachloride 

Halogen type refrigerants 

Cleaning solvents (such as perchloroethylene) 

Printing inks, paint removers, varnishes, etc. 

Hydrochloric acid 

Cements and glues 

Antistatic fabric softeners for clothes dryers 

Masonry acid washing materials 

When outdoor air is used for combustion, the combustion air intake duct
system termination must be located external to the building and in an
area where there will be no exposure to the substances listed above.

CODES AND STANDARDS

Follow all national, local codes and standards in addition to this installa-
tion manual. The installation must comply with regulations of the serv-
ing gas supplier, local building, heating, plumbing, and other codes. In
absence of local codes, the installation must comply with the national
codes listed below and all authorities having jurisdiction.

In the United States and Canada, follow all codes and standards for the
following, using the latest edition available:

STEP 1 -Safety

US: National Fuel Gas Code (NFGC) NFPA 54/ANSI Z223.1 and
the Installation Standards, Warm Air Heating and Air Conditioning
Systems ANSI/NFPA 90B

CANADA: CAN/CGA-B149.1 National Standard of Canada. Natu-
ral Gas and Propane Installation Codes (NSCNGPIC)

STEP 2 -General Installation

US: Current edition of the NFGC and NFPA 90B. For copies, con-
tact the 

National Fire Protection Association Inc.
Batterymarch Park
Quincy, MA 02269

or for only the NFGC, contact the 

American Gas Association, 
400 N. Capital, N.W. 
Washington DC 20001 

or www.NFPA.org

CANADA: NSCNGPIC. For a copy contact:

Standard Sales, CSA International
178 Rexdale Boulevard
Etobicoke, (Toronto) Ontario Canada M9W 1RS

STEP 3 -Combustion and Ventilation Air

US: Section 5.3 of the NFGC, air for Combustion and Ventilation

CANADA: Part 7 of NSCNGPIC, Venting Systems and Air Supply
for Appliances

STEP 4 -Duct Systems

US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors
Association National Association (SMACNA), or American Soci-
ety of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 1997 Fundamentals Handbook Chapter 32.

STEP 5 -Acoustical Lining and Fibrous Glass Duct

US and CANADA: Current edition of SMACNA and NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts

STEP 6 -Gas Piping and Gas Pipe Pressure Testing

US: NFGC; chapters 2, 3, 4, & 9 and National Plumbing Codes

CANADA: NSCNGPIC Part 5

STEP 7 -Electrical Connections

US: National Electrical Code (NEC) ANSI/NFPA 70

CANADA: Canadian Electrical Code CSA C22.1

These instructions cover minimum requirements and conform to exist-
ing national standards and safety codes. In some instances these
instructions exceed certain local codes and ordinances, especially
those who have not kept up with changing residential and non-HUD
modular home construction practices. These instructions are required
as a minimum for a safe installation.

 WARNING

The furnace area must not be used as a broom closet or for any other
storage purposes, as a fire hazard may be created. Never store items
such as the following on, near or in contact with the furnace.

1. Spray or aerosol cans, rags, brooms, dust mops, vacuum clean-

ers or other cleaning tools.

2. Soap powders, bleaches, waxes or other cleaning compounds;

plastic items or containers; gasoline, kerosene, cigarette lighter
fluid, dry cleaning fluids or other volatile fluid.

3. Paint thinners and other painting compounds.

4. Paper bags, boxes or other paper products

Never operate the furnace with the blower door removed. To do
so could result in serious personal injury and/or equipment
damage.

!

Summary of Contents for TM8V C Series

Page 1: ...les All Dimensions in Inches and All Surfaces Identified with the Unit in an Upflow Configuration 4 Coil Projection Dimensions PC Series Coils 6 Cabinet and Duct Dimensions 9 Recommended Filter Sizes...

Page 2: ...provided that the tubes are lifted at the front of the heat exchangers where attached to the vestibule panel Do not use the top return bend of the heat exchangers as lift ing points as the tubes may...

Page 3: ...e National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or for only the NFGC contact the American Gas Association 400 N Capital N W Washington DC 20001 or www NFPA org CANADA NSCN...

Page 4: ...ide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed In addition the installing plumber or gasfitter shall observe that a battery o...

Page 5: ...all be attached in such a manner as to prevent leaks DUCT FLANGES Four flanges are provided to attach ductwork to the furnace These flanges are rotated down for shipment In order to use the flanges re...

Page 6: ...furnace A mounting plate supplied with every coil should always be installed on the side desig nated as top side See Figures 4 5 FURNACE ASSEMBLY PC SERIES COILS Dimension C should be at least 2 3 of...

Page 7: ...r installation RESIDENTIAL AND MODULAR HOME UPFLOW RETURN PLENUM CONNECTION Return air may enter the furnace through the side s or bottom depend ing on the type of application Return air may not be co...

Page 8: ...mum clearance between the front of the furnace and the support rods or straps All six suspension points must be level to ensure proper and quiet fur nace operation When suspending the furnace use a se...

Page 9: ...Y END C 24 38 20 5 B Gas Pipe Entry Thermostat Wiring 33 A 5 Electrical Entry Vent Connection Outlet Vent Connection Outlet 4 Diameter Outlet Vent Connection Table 3 Cabinet and Duct Dimensions BTUH k...

Page 10: ...he type of gas approved for this furnace only use those approved gases The instal lation of a drip leg and ground union is required Refer to Figure 15 FIGURE 13 Side Return Cutout Markings IMPORTANT S...

Page 11: ...2742 2743 3048 Gas Heating Value BTU cu ft 800 3 5 3 5 3 5 Gas Heating Value MJ cu m 29 8 0 87 0 87 0 87 850 3 5 3 5 3 5 31 7 0 87 0 87 0 87 900 3 5 3 5 3 5 33 5 0 87 0 87 0 87 950 3 5 3 5 3 3 35 4 0...

Page 12: ...l thermostat and outdoor A C or heat pump using either conventional low voltage 24 VAC thermo stat wiring OR using four wire digital communications wiring To use conventional low voltage wiring see th...

Page 13: ...h may be connected to the FLT SWT terminals on the control board This feature is only functional when used with the Com munication Control It is intended for use with a water overflow switch Auxiliary...

Page 14: ...to Communication Control Installation Man ual LOW VOLTAGE CONTROL WIRING CONNECTIONS Install the field supplied thermostat by following the instructions that come with the thermostat With the thermost...

Page 15: ...s for all UPG equipment refer to Low Voltage System Wiring document available on line at www upgnet com in the Product Catalog Section FIGURE 21 Thermostat Chart Single Stage Air Conditioner with Two...

Page 16: ...ls Unitary Products FIGURE 22 Thermostat Chart Single Stage Heat Pump with Two Stage Variable Speed Furnace Y Y2 TM8V W1 Room thermostat or external fossil fuel kit must be used to control fossil fuel...

Page 17: ...5402847 UIM A 0917 Johnson Controls Unitary Products 17 FIGURE 23 Thermostat Chart Two Stage Air Conditioner with Two Stage Variable Speed Furnace A0918 001 TM8V S1 THXU280 W1 TMLV...

Page 18: ...02847 UIM A 0917 18 Johnson Controls Unitary Products FIGURE 24 Thermostat Chart Two Stage Heat Pump with Two Stage Variable Speed Furnace Hot Heat Pump or Conventional TM8V S1 THXU280 W1 A0919 001 TM...

Page 19: ...rate appliance designed to burn solid fuel It is recommended that the appliance is installed in a location where the space temperature is 32 F 0 C or higher If the appliance is installed in a locatio...

Page 20: ...no dimen sion smaller than 0 25 0 64 cm 3 A manually operated damper or manually adjustable louvers are not permitted for use 4 A automatically operated damper or automatically adjustable lou vers sh...

Page 21: ...onal area as the free area of the air supply inlet opening to which it connects 4 The blocking effects of louvers grilles and screens must be given consideration in calculating free area If the free a...

Page 22: ...ng placed into operation while all other appliances connected to the venting system are not in operation 1 Inspect the venting system for proper size and horizontal pitch Determine that there is no bl...

Page 23: ...clocking meter 1 Turn off all other gas appliances and pilots 2 Run furnace for a minimum of 3 minutes in heating operation 3 Measure time in sec for gas meter to complete 1 revolution and note readi...

Page 24: ...Size of Test Dial Seconds For 1 Revolution Size of Test Dial 1 Cu Ft 2 Cu Ft 5 Cu Ft 1 Cu Ft 2 Cu Ft 5 Cu Ft 10 360 720 1800 50 72 144 360 11 327 655 1636 51 71 141 355 12 300 600 1500 52 69 138 346...

Page 25: ...pplies back on and with the burners in operation check for gas leakage around the gas valve pressure port for leakage using an approved non corrosive gas leak detec tion fluid or other non flammable l...

Page 26: ...is dependent upon the panel that covers the blower compartment being in place and properly positioned ROLLOUT SWITCH CONTROLS These controls are mounted on the burner assembly If the temperature in th...

Page 27: ...l run at the speed selected on the FAN SPEED jumpers on the main control board HI COOL LO COOL HI HEAT or LO HEAT When the jumper is in the VS G position the blower will run at 50 of the high cool spe...

Page 28: ...ce will lock out for one hour and then restart 9 RED FLASHES Indicates reversed line voltage polarity grounding problem or reversed low voltage transformer wires Both heating and cooling operations wi...

Page 29: ...3 D A 1013 676 1245 842 1284 842 C C 844 591 1092 765 1130 746 D C HIGH LOW HEAT CFM 060B12 080B12 080C16 Jumper Settings HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HIGH HEAT LOW HEAT HEAT Tap ADJ Tap 1111...

Page 30: ...L Models Only MISCELLANEOUS ORIFICE BURNER Natural 45 SIGHT GLASS OVAL 2 Req d GASKET FOAM Door 1 5 ft Req d GASKET INTAKE PAN PLUG VENT HOLE BRACKET DOOR WIRING HARNESS FERRULE 3 Req d GROMMET 3 Req...

Page 31: ...of flame during call for heat Hot Neutral reversed OR poor ground neutral Gas valve shorted ON Check blower motor wiring Vent OR termination problem None Slow Green Slow Amber Rapid Amber 4 Amber Ste...

Page 32: ...5402847 UIM A 0917 32 Johnson Controls Unitary Products NOTES...

Page 33: ...Equipment and Accessories Owner Information Equipment Data Furnace Configuration Venting B Vent Electrical Line Voltage Outdoor Unit Model Outdoor Unit Serial Filter Thermostat Accessories Filter Loc...

Page 34: ...Side Continuous Fan PSC Clean Up Give owner the owner s manual provided Gas Type Explain thermostat use and programming if applicable to owner Cycle Test Operate the furnace through several heating c...

Reviews: