JOHNSON CONTROLS
62
Physical Data
(SI - High Efficiency)
Refrigerant R-134a
HIGH EFFICIENCY
MODEL NUMBER (YCIV____ E/V)
General Unit Data
60Hz
0157
0177
0187
0197
0207
0227
0247
50Hz
0590
0630
0700
0760
0800
0830
0930
Number of Independent Refrigerant Circuits
2
2
2
2
2
2
2
Refrigerant Charge, R-134a, Ckt.-1/Ckt.-2, kg.
77/77
84/77
84/84
87/87
102/87
102/102
105/105
Oil Charge, Ckt.-1/Ckt.-2, liters
19/19
19/19
19/19
19/19
19/19
19/19
19/19
Compressors, Semihermetic Screw Qty per Chiller
2
2
2
2
2
2
2
Condensers, High Efficiency Fin/Tube with Integral Subcooler
Total Chiller Coil Face Area, m2
21.8
24.5
27.2
27.2
30.0
32.7
32.7
Number of Rows
3
3
3
3
3
3
3
Fins per meter
669
669
669
669
669
669
669
Condenser Fans
Number, Ckt.-1/Ckt.-2
4/4
5/4
5/5
5/5
6/5
6/6
6/6
Low Sound Fans
Fan Motor, HP/kWi
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
Total Chiller Airflow, l/sec.
49082
55218
61353
61353
67488
73624
73624
Ultra Quiet Fans
Fan Motor, HP/kWi
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
2/1.50
Total Chiller Airflow, l/sec.
49082
55218
61353
61353
67488
73624
73624
Dual Speed Fans - Normal Speed
Fan, KWi
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Total Chiller, m3/s
42
47
52
52
57
62
62
Dual Speed Fans - Lower Speed
Fan, KWi
1.5
1.5
1.5
1.5
1.5
1.5
1.5
Total Chiller, m3/s
32
36
40
40
44
48
48
High Static Fans
Fan, KWi
3.7
3.7
3.7
3.7
3.7
3.7
3.7
Total Chiller, m3/s
49
55
61
61
67
74
74
Evaporator, Direct Expansion
Water Volume, liters
359.6
359.6
359.6
416.4
416.4
416.4
529.9
Maximum Water Side Pressure, Bar
1
10
10
10
10
10
10
10
Maximum Refrigerant Side Pressure, Bar
16
16
16
16
16
16
16
Minimum Chilled Water Flow Rate, l/sec.
10.1
10.1
10.1
11.4
11.4
11.4
11.4
Maximum Chilled Water Flow Rate, l/sec.
47.3
47.3
47.3
47.3
47.3
47.3
50.5
Water Connections, inches
10
10
10
10
10
10
10
Contact your nearest Johnson Controls Sales Office for weight data.
Summary of Contents for UL R134A
Page 115: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 115 INTENTIONALLY LEFT BLANK...
Page 127: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 127 INTENTIONALLY LEFT BLANK...
Page 128: ...JOHNSON CONTROLS 128 Typical Control Wiring Two Compressor...
Page 130: ...JOHNSON CONTROLS 130 Typical Control Wiring Three Compressor...
Page 138: ...JOHNSON CONTROLS 138...
Page 139: ...JOHNSON CONTROLS FORM 201 23 EG1 1007 139...
Page 140: ...Form 201 23 EG1 1007 Supersedes 201 23 EG1 607 File in ET2...