9. Electric Characteristics
YUHA 18 FT
YUHA 24 FT
YUHA 36 FT
YUHA 36 FT
YUHA 48 FT
Symbols:
MCA: Min. Circuit Amps.
MFA: Max. Fuse Amps..
FLA: Full Load Amps.
Kw: Rate Motor Output
Notes:
7. Voltage range should not over the value of above table.
8. Maximum allowable voltage variation between phase is 2%
9. Selection wire size based on the larger value of MCA.
10. MCA/MFA
MCA = 1.25 × FLA
MFA
≤
4 × FLA
(Next lower standard fuse rating min. 15A)
5. Instead of fuse, circuit breaker is also acceptable.
Indoor Units
Power Supply
Indoor fan motor
Power input(W)
Model
Hz
Voltage
Min. Max.
MCA
MFA
kW
FLA
Cooling
Heating
13.5
40
0.06
0.54
2100
2100
16.7
50
0.07
0.78
2510
2500
220~240
198
264
26.2
80
0.06
0.52
3700
3550
8.1
30
0.06
0.52
3700
3550
50
380
342
418
11.5
30
0.06
0.52
5400
5500