36
Load Flow Rates
Model
Minimum Load Flow Rate
Normal Load Flow Rate
Maximum Flow Rate
018
3.0
5.0
7.0
025
4.0
7.0
9.0
040
5.0
10.0
12.0
050
8.0
15.0
17.0
060
9.0
18.0
20.0
075
10.0
19.0
21.0
5/15/09
Flow Rates
Source Flow Rates
Model
Minimum Open Loop
Flow Rate
Minimum Closed Loop
Flow Rate
Normal Load Flow Rate
Maximum Flow Rate
018
3.0
4.0
5.0
7.0
025
4.0
5.0
7.0
9.0
040
5.0
8.0
10.0
12.0
050
8.0
12.0
15.0
17.0
060
9.0
13.0
18.0
20.0
075
10.0
14.0
19.0
21.0
5/15/09
Thermistor Table
Thermistor Temperature (°F)
Resistance (Ohms)
78.8
9,230 - 10,007
77.5
9,460 - 10,032
76.5
9,690 - 10,580
75.5
9,930 - 10,840
33.5
30,490 - 32,080
32.5
31,370 - 33,010
31.5
32,270 - 33,690
30.5
33,190 - 34,940
1.5
79,110 - 83,750
0.5
81,860 - 86,460
0.0
82,960 - 87,860
Compressor Resistance Table (77°F)
Terminals
018
ZP16K5E
025
ZP25KSE
040
HRH034U
050
ZP51K5E
060
HRH056U
075
HLJ072T
C to S
2.14 - 2.28
1.77-2.03
1.30 - 1.49
0.74 - 0.85 0.76 - 0.88 0.78 - 0.90
C to R
1.42 - 1.64
0.95-1.09
0.49 - 0.57 0.42 - 0.48 0.26 - 0.30 0.27 - 0.31
S to R
3.56 - 4.10
2.72-3.12
1.79 - 2.06
1.16 - 1.33
1.02 - 1.18
1.05 - 1.21
1/15/15
NOTE:
Resistance listed are for single phase (208-230/60Hz) compressors.
Thermistor and Compressor Resistance
Physical Data
Model
018
025
040
050
060
075
Compressor (1 each)
Scroll
Factory Charge R410a, oz [kg]
44.0 [1.25]
58.0 [1.64]
70 [1.98]
68 [1.93]
104 [2.95]
110 [3.12]
Coax & Piping Water Volume - gal [l]*
.52 [1.97]
.89 [3.38]
1.0 [3.94]
1.4 [5.25]
1.6 [6.13]
1.6 [6.13]
Weight - Operating, lb [kg]
191 [86.6]
225 [102.1]
290 [131.5]
325 [147.4]
345 [156.5]
345 [156.5]
Weight - Packaged, lb [kg]
213 [96.6]
247 [112.0]
305 [138.3]
340 [154.2]
360 [163.3]
360 [163.3]
8/6/10
NOTE:
* Source or load side only.
AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL
Summary of Contents for YAWS018 - 075
Page 2: ......
Page 50: ...50 Notes AFFINITY SINGLE STAGE HYDRONIC INSTALLATION MANUAL ...