JOHNSON CONTROLS
48
FORM 150.66-NM3
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
OPERATIONAL LIMITATIONS (SI)
LD13318
SI
1
10
100
1000
1
10
100
FLOW, L/S
P
re
ss
D
ro
p,
k
P
A
B
A
C
D
HEAT EXCHANGER FLOW, L/S
MODEL YCAL
COOLER CURVE
0041
A
0045,0051
B
0055
C
0061,0065, 0071
D
Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges.
See “Design Parameters” in Engineering
Guide (150.64-EG1) for minimum and maximum flowpoints.
TABLE 7 – ETHYLENE GLYCOL CORRECTION FACTORS
% WT
ETHYLENE
GLYCOL
FACTORS
FREEZE
POINT
(°F)
TONS
COMPR.
kW
DELTA
P
GPM/°F/TON
10
.994
.997
1.03
24.1
26
20
.986
.993
1.06
24.9
16
30
.979
.990
1.09
25.9
5
40
.970
.985
1.13
27.3
-10
50
.959
.980
1.16
29.0
-32
Summary of Contents for YCAL Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 144: ...JOHNSON CONTROLS 144 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 173: ...FORM 150 66 NM3 ISSUE DATE 09 25 2020 173 JOHNSON CONTROLS 10 NOTES...