JOHNSON CONTROLS
152
FORM 150.66-NM3
ISSUE DATE: 09/25/2020
SECTION 9 - SERVICE AND TROUBLESHOOTING
The suction transducers have a range from 0 psig to
400 psig (27.58 barg). The output will be linear from
0.5 VDC to 4.5 VDC over the 400 psig (27.58 barg)
range. Following is a formula that can be used to verify
the voltage output of the transducer. All voltage read-
ings are in reference to ground (unit case).
V = (Pressure in psig x 0.01) + .5
or
V = (Pressure in BARG x 0.145) + .5
where V = dc voltage input to microprocessor
Pressure = pressure sensed by transducer
Following are the microboard connections for the Suc-
tion Transducer:
System 1 Suction Transducer
J7-5 = +5 VDC regulated supply to transducer.
J7-10 = VDC input signal to the microboard.
See the formula above for voltage readings that cor
-
respond to specific suction pressures.
J7-9 = +5 VDC return
J7-1 = drain (shield connection = 0 VDC)
System 2 Suction Transducer
J9-5 = +5 VDC regulated supply to transducer.
J9-10 = VDC input signal to the microboard.
See the formula above for voltage readings that cor
-
respond to specific suction pressures.
J9-9 = +5 VDC return
J9-1 = drain (shield connection = 0 VDC)
Digital Outputs
Refer to the unit wiring diagram and Fig. 20.
The digi-
tal outputs are located on TB-7, TB-8, TB-9 and TB-
10 of the microboard.
ALL OUTPUTS ARE 120VAC
with the exception of TB8-6 to TB8-7 which are the
contacts that can be used for a remote evaporator pump
start signal. The voltage applied to either of these ter-
minals would be determined by field wiring.
Each output is controlled by the microprocessor by
switching 120 VAC to the respective output connection
energizing contactors, evaporator heater, and solenoids
according to the operating sequence.
120VAC is supplied to the I/O board via connections
at TB7-1, TB7-6, TB10-1, TB10-6, TB8-1, and TB9-1.
Fig. 20 illustrates the relay contact architecture on the
microboard.
FIG. 20 – MICROBOARD RELAY CONTACT
ARCHITECTURE
LD12722
SYS 1
COMP 1
TB7-2
SYS 1
COMP 2
TB7-4
SYS 1
COMP 3
TB7-5
TB7-3
LLSV 1
TB8-6
EVAP
PUMP
TB8-7
TB7
SYS 2
HGSV
TB10-7
SYS 2
FAN 2
TB10-8
TB10-9
TB10-10 SYS 2
FAN 4
TB10
TB8
TB10
SYS 2
COMPR 1 (4)
TB10-2
LLSV 2
TB10-3
SYS 2
COMPR 2 (5)
TB10-4
SYS 2
COMPR 3 (6)
TB10-5
TB7
SYS 1
HGSV
TB7-7
SYS 1
FAN 1
TB7-9
SYS 1
FAN 3
TB7-10
TB7-8
SYS 1
FAN 2
TB8-2
HEAT EXCH
HEATER
Summary of Contents for YCAL Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 144: ...JOHNSON CONTROLS 144 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 173: ...FORM 150 66 NM3 ISSUE DATE 09 25 2020 173 JOHNSON CONTROLS 10 NOTES...