JOHNSON CONTROLS
64
FORM 150.66-NM3
ISSUE DATE: 09/25/2020
SECTION 6 - TECHNICAL DATA
VIEW B-B
3 15/16"
3 1/4"
6 3/4"
BOTTOM OF PANEL
7/8" TYP.
47 3/4"
46 15/16"
45 1/8"
12 5/8"
3" VICTAULIC (typ)
90 1/4" BASE WIDTH
LEFT END
LIQUID OUT
34 5/8"
15 3/4"
9 15/16"
ELECTRICAL ACCESS
PANEL
LIQUID IN
LD10962
DIMENSIONS - YCAL0041 (ENGLISH)
NOTE:
Placement on a level surface free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 6';
rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'. No
more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by 6".
ALUMINUM
COPPER
YCAL
CENTER OF GRAVITY (IN.)
YCAL
CENTER OF GRAVITY (IN.)
X
Y
X
Y
0041
59.6
43.6
0041
63.6
43.7
DIMENSIONS
Summary of Contents for YCAL Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 130: ...JOHNSON CONTROLS 130 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 144: ...JOHNSON CONTROLS 144 FORM 150 66 NM3 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 173: ...FORM 150 66 NM3 ISSUE DATE 09 25 2020 173 JOHNSON CONTROLS 10 NOTES...