JOHNSON CONTROLS
154
FORM 150.66-NM2
ISSUE DATE: 09/25/2020
SECTION 9 - SERVICE AND TROUBlEShOOTING
PROBLEM
CAUSE
SOLUTION
“MP / HPCO” FAULT
1. Compressor internal motor
1. Verify refrigerant charge is
protector (MP) open.
not low. Verify superheat
setting of °10 - 15°F (5.6° -
8. 3°C). Verify correct com-
pressor rotation. Verify
compressor is not over
loaded.
2. External overload tripped.
2. Determine cause and reset.
3. hPCO switch open.
3.
See “High Press. Disch.”
Fault.
4. Defective hPCO switch.
4. Replace hPCO switch.
5. Defective CR relay.
5. Replace relay.
COMPRESSOR(S) WON’T
1. Demand not great enough.
1. No problem. Consult
START
“Installation” Manual to aid
in understanding compres-
sor operation and capacity
control.
2. Defective water temperature
2. Compare the display with a
sensor.
thermometer. Should be
/- 2 degrees.
Refer
to Service section for RWT/
LWT temp./voltage table
.
3. Contactor/Overload failure.
3. Replace defective part.
4. Compressor failure.
4. Diagnose cause of failure
and
replace.
LACK OF COOLING EFFECT
1. Fouled evaporator surface.
1. Contact the local yORK
low suction pressure will
service representative.
be observed.
2. Improper flow through the
2. Reduce flow to within chiller
evaporator.
design
specs.
See Limita-
tions in Installation section.
3. low refrigerant charge.
3. Check subcooling and add
low suction pressure will
charge as needed.
be observed.
TROUBLESHOOTING (CONT’D)
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...