TABLE 32 – ISN TRANSMITTED DATA
ISN
PAGE
CHARACTER
TYPE
DATA
P11
8-11
Analog leaving Chilled
liquid Temp.
P12
12-15
Analog Return Chilled
liquid Temp.
P13
16-19
Analog
---
P14
20-23
Analog
---
P15
24-27
Analog SyS 1 Suction
Temp. (EEV Only)
P16
28-31
Analog Ambient Air Temp.
P17
32-35
Analog
SyS 1 Suction
Superheat
(EEV Only)
P18
36-39
Analog SyS 1 Run Time
(Seconds)
P19
40-43
Analog SyS 1 Suction
Superheat
P20
44-47
Analog SyS 1 Discharge
Pressure
P21
48-51
Analog
---
P22
52-55
Analog
---
P23
56-59
Analog
SyS 1 EEV
Output %
(EEV Output)
P24
60-63
Analog SyS 1
Anti-Recycle Timer
P25
64-67
Analog Anti-Coincidence
Timer
P26
68-71
Analog Spare
P27
72-75
Analog Spare
P28
76-79
Analog Spare
P29
80-83
Analog Spare
P30
84-87
Analog Spare
P31
88-91
Analog
---
P32
92-95
Analog Spare
P33
96-99
Analog Spare
P34
100-103
Analog Spare
P35
104-107
Analog # of Compressors
P36
108
Digital SyS 1 Alarm
P37
109
Digital Spare
P38
110
Digital Evaporator heater
Status
P39
111
Digital Evaporator Pump
Status
P40
112
Digital SyS 1
Comp. 2 Run
RECEIVED DATA (CONTROL DATA)
The Middle Market receives 8 data values from the
ISN. The first 4 are analog values and the last 4 are
digital values. These 8 data values are used as control
parameters when in REMOTE mode. When the unit is
in LOCAL mode, these 8 values are ignored. If the unit
receives no valid ISN transmission for 5 minutes it will
revert back to all local control values. Table 31 lists
the 5 control parameters. These values are found under
feature 54 on the ISN.
TRANSMITTED DATA
After receiving a valid transmission from the ISN, the
unit will transmit either operational data or history buffer
data depending on the “History Buffer Request” on
ISN PAGE 10. Data must be transmitted for every ISN
page under feature 54. If there is no value to be sent to
a particular page, a zero will be sent. Tables 32-33 show
the data values and page listings for this unit.
ISN PAGES listed are ENG PAGE
REFERENCES and must be decod
ed to the corresponding PAGE REF
point map related to the communica
tions protocol type utilized. The latest
point map information is listed on the
Johnson Controls Group Equipment
Integration website.
ISN
CONTROL DATA
PAGE
P03
SETPOINT
99
=
AUTO
P04
lOAD lIMIT STAGE (0, 1, 2)
P05
–
P06
–
P07
START/STOP COMMAND
(0 = STOP, 1 = RUN)
P08
—
P09
—
P10
hISTORy BUFFER REQUEST
(0 = CURRENT DATA, 1 = lAST hISTORy DATA)
TABLE 31 – ISN RECEIVED DATA
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...