SECTION 10 - MAINTENANCE
T
ABLE 32 – ISN TRANSMITTED DATA (CONT’D)
ISN CONTROL (CON’T)
ISN
PAGE
CHARACTER
TYPE
DATA
P41
113
Digital Spare
P42
114
Digital
SyS 1 liquid line
Solenoid Valve or
EEV Pilot Solenoid
P43
115
Digital SyS 1 hot Gas
Bypass Valve
P44
116
Digital SyS 1
Comp. 2 Run
P45
117
Digital Spare
P46
118
Digital Spare
P47
119
Digital Spare
P48
120
Digital SyS 1
Comp.3 Run
P49
121
Digital SyS 2
Comp. 3 Run
P50
122
Digital Chilled liquid Type
(0=Water, 1=Glycol)
P51
123
Digital
Ambient Control Mode
(0=Std. Ambient,
1=low Ambient)
P52
124
Digital
local/Remote
Control Mode
(0=local,
1=Remote)
P53
125
Digital Units
(0=Imperial, 1= SI)
P54
126
Digital
lead/lag Control
Mode
(0=Manual,1= Remote)
P55
127
Digital -
P56
128
Coded * SyS 1
Operational Code
P57
129
Coded * SyS 1
Fault Code
P58
130
Coded Spare
P59
131
Coded Spare
P60
132
Coded -
P61
133
Coded SyS 1 Condenser
Fan Stage
ISN
PAGE
CHARACTER
TYPE
DATA
P62
134
Coded -
P63
135
Coded Spare
P64
136
Coded -
P65
137
Coded
Unit Control Mode
(0=leaving Water,
1=Return Water,
2=Discharge Air,
3=Suction Press.,
4=Cooling
5=heating)
P66
138-141
Analog Anti-Recycle Timer
P67
142-145
Analog leaving Chilled liquid
Temp. Cutout
P68
146-149
Analog low Ambient
Temp. Cutout
P69
150-153
Analog -
P70
154-157
Analog low Suction
Pressure Cutout
P71
158-161
Analog high Discharge
Pressure Cutout
P72
162-165
Analog Setpoint
P73
166-169
Analog Cooling Range
P74
170-173
Analog -
P75
174-177
Analog -
P76
178-181
Analog
SyS 1 Discharge
Temp.
(EEV Only-Optional)
P77
182-185
Analog
SyS 1 Discharge
Superheat
(EEV Only- Optional)
P78
186-189
Analog Spare
P79
90-193
Analog Spare
P80
194
Digital -
P81
195
Digital -
P82
196
Digital -
P83
197
Digital -
P84
198
Digital -
* The operational and fault codes sent to pages 56 through 59 are defined in Table 33. Note that this table of fault and operational codes is for
all DX products.
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...