FORM 150.66-NM2
ISSUE DATE: 09/25/2020
53
JOHNSON CONTROLS
SECTION 6 - TEChNICAl DATA
6
SINGlE POINT FIElD SUPPlIED POWER WIRING
(See FIG. 5)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional)).
ELECTRICAL DATA YCAL0012 - 0032 (ENGLISH) (CON’T)
Disc. Switch
Lug Wire
Range
Lugs/
Phase
Circuit
Breaker
Lug Wire
Range
Lugs/
Phase
Short
Circuit
Terminal
Block
Short
Circuit
NF
Discon
Short
Circuit
Breaker
Compressors & Fans
Compr. #1
Compr. #2
Num.
of
Fans
Fans (Std)
Fans (Low
Noise)
RLA
LRA RLA LRA
FLA
LRA
FLA
LRA
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
20.4
150
20.4
150
2
2.6
5.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
18.8
150
18.8
150
2
2.6
5.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
10.9
91
10.9
91
2
1.6
3.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
9.0
75
9.0
75
2
1.3
2.5
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
7.2
100
7.2
100
2
1.0
2.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
35.2
250
35.2
250
2
2.6
5.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
32.6
250
32.6
250
2
2.6
5.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
18.8
155
18.8
155
2
1.6
3.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
15.5
125
15.5
125
2
1.3
2.5
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
12.4
100
12.4
100
2
1.0
2.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
39.1
250
39.1
250
2
2.6
5.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
36.2
250
36.2
250
2
1.6
5.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
20.9
155
20.9
155
2
1.6
3.0
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
17.2
125
17.2
125
2
1.3
2.5
—
—
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
13.8
100
13.8
100
2
1.3
2.5
—
—
(1) #14 -#1/0
1
(1) #14 -#1/0
1
5kA
5kA
5kA/65kA
49.4
316
49.4
316
2
7.6
30.9
8.9
22.8
(1) #14 -#1/0
1
(1) #14 -#1/0
1
5kA
5kA
5kA/65kA
45.8
316
45.8
316
2
7.4
37.0
6.0
22.8
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
26.4
199
26.4
199
2
4.5
22.3
4.5
12.7
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
21.8
158
21.8
158
2
4.0
19.0
3.4
21.0
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
17.4
126
17.4
126
2
2.9
14.6
3.0
8.3
(1) #14 -#1/0
1
(1) #14 -#1/0
1
5kA
5kA
5kA/65kA
49.4
316
49.4
316
2
7.6
30.9
8.9
22.8
(1) #14 -#1/0
1
(1) #14 -#1/0
1
5kA
5kA
5kA/65kA
45.8
316
45.8
316
2
7.4
37.0
6.9
22.8
(1) #14 -#1/0
1
(1) #14 -#1/0
1
5kA
5kA
5kA/65kA
26.4
199
26.4
199
2
4.5
22.3
4.5
12.7
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
21.8
158
21.8
158
2
4.0
19.0
3.4
21.0
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
17.4
126
17.4
126
2
2.9
14.6
3.0
8.3
(1) #14 -#1/0
1
(1) #14 -#1/0
1
5kA
5kA
5kA/65kA
53.8
425
49.4
316
2
7.6
30.9
8.9
22.8
(1) #14 -#1/0
1
(1) #14 -#1/0
1
5kA
5kA
5kA/65kA
49.8
425
45.8
316
2
7.4
37.0
6.9
22.8
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
28.7
239
26.4
199
2
4.5
22.3
4.5
12.7
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
23.7
198
21.8
158
2
4.0
19.0
3.4
21.0
(1) #14 -#2
1
(1) #14 -#2
1
5kA
5kA
5kA/65kA
19.0
148
17.4
126
2
2.9
14.6
3.0
8.3
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...