JOHNSON CONTROLS
132
FORM 150.66-NM2
ISSUE DATE: 09/25/2020
SECTION 8 - UNIT OPERATION
TABLE 20 – YCAL0012 – YCAL0032 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY
TABLE 19 – YCAL0012 – YCAL0032 CONDENSER FAN CONTROL USING OUTDOOR AMBIENT
TEMPERATURE AND DISCHARGE PRESSURE (DISCHARGE PRESSURE CONTROLS WILL
NOT FUNCTION AND FAN CONTROL WILL BE BASED ON AMBIENT TEMPERATURES ONLY,
UNLESS THE OPTIONAL DISCHARGE PRESSURE TRANSDUCER IS INSTALLED).
lD12211
STANDARD CONDENSER FAN CONTROL - YCAL0012 – YCAL0032
FAN
STAGE
ON
OFF
CONTACTOR
MICROBOARD
OUTPUT
FAN #
1
OAT > 25°F (-3.9°C)
or
DP> Fan Ctrl On
Press
OAT < 20°F (6.7°C)
and
DP < Fan Ctrl On
Press - (Diff. Press)
7M
TB7-9
3
2
OAT > 65°F (18.3°C)
or
DP > Fan Ctrl On
Press
+75 psig (5.17 bar)
OAT < 60°F (15.6°C)
and
DP < Fan Ctrl On
Press -
(Diff. Press + 75 psig
(5.17 bar))
7M
&
8M
TB7-9
&
TB7-10
1
&
3
FAN
STAGE
ON
OFF
CONTACTOR
MICROBOARD
OUTPUT
FAN #
1
DP > Fan Ctrl
On Press
DP < Fan Ctrl On
Press - (Diff. Press.)
7M
TB7-9
3
2
DP > Fan Ctrl On
Press +
75 psig (5.17 bar)
DP < Fan Ctrl On
Press - ((Diff. Press.)
+ 75 psig
(5.17 bar))
7M
&
8M
TB7-9
&
TB7-10
1
&
3
FAN #1
FAN #2
Summary of Contents for YCAL0012EC
Page 12: ...JOHNSON CONTROLS 12 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 16: ...JOHNSON CONTROLS 16 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 98: ...JOHNSON CONTROLS 98 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 142: ...JOHNSON CONTROLS 142 FORM 150 66 NM2 ISSUE DATE 09 25 2020 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 165: ...FORM 150 66 NM2 ISSUE DATE 09 25 2020 165 JOHNSON CONTROLS NOTES...