FORM 150.67-NM2 (209)
177
JOHNSON CONTROLS
9
SYS 1 COMP 3 STATUS TB7-5 IS:
SYS 1 HGBP STATUS TB7-7 IS:
SYS 2 COMP 1 STATUS TB10-2 IS:
SYS 2 LLSV STATUS TB10-3 IS:
SYS 2 COMP 2 STATUS TB10-4 IS:
SYS 2 COMP 3 STATUS TB10-5 IS:
SYS 1 FAN OUTPUT 1 TB7-8 IS:
SYS 1 FAN OUTPUT 2 TB7-9 IS:
SYS 1 FAN OUTPUT 3 TB7-10 IS:
SYS 2 FAN OUTPUT 1 TB10-8 IS:
SYS 2 FAN OUTPUT 2 TB10-9 IS:
SYS 2 FAN OUTPUT 3 TB10-10 IS:
EVAP HEATER STATUS TB8-2 IS:
SYS 1 ALARM STATUS TB8-3 IS:
SYS 2 ALARM STATUS TB9-2 IS:
EVAP PUMP STATUS TB8-6,7 IS:
SYS 2 HGBV STATUS TB10-7 IS:
SPARE DO TB8-4 IS:
SPARE DO TB8-5 IS:
SPARE DO TB8-8, 9 IS:
SPARE DO TB9-4 IS:
SYS 1 EEV OUTPUT TB5-1, 2 = XXX%
SYS 2 EEV OUTPUT TB6-1, 2 = XXX%
SYS 1 COND FAN SPEED J15-1,5 = XXX%
SYS 2 COND FAN SPEED J15-2,6 = XXX%
SPARE AO J15-3,7 = XXX%
SPARE AO J15-4,8 = XXX%
DATA LOGGING MODE 1 = ON, 0 = OFF
DATA LOGGING TIMER X SECS
SOFT START (disabled)
REFRIGERANT TYPE (R410A only)
EXPANSION VALVE TYPE (Thermostatic Only)
REMOTE TEMP RESET OPTION =
REMOTE INPUT SERVICE TIME =
“NORTH AMERICAN FEATURE SET ENABLED”
HYDRO PUMP SELECTION
EVAP PUMP TOTAL RUN HOURS
SYS 1 HOURS
SYS 2 HOURS
SYS 1 STARTS
SYS 2 STARTS
Each display will also show the output connection on
the microboard for the respective output status shown.
For example:
This display indicates that the system 1 liquid line sole-
noid valve is OFF, and the output connection from the
microboard is coming from terminal block 10 – pin 3.
SECTION 9 – SERVICE AND TROUBLESHOOTING
CLEARING HISTORY BUFFERS
The history buffers may be cleared by pressing the HIS-
TORY key and then repeatedly pressing the UP arrow
key until you scroll past the last history buffer choice.
The following message will be displayed:
Pressing the ENTER/ADV key at this display will cause
the history buffers to be cleared. Pressing any other key
will cancel the operation.
DO NOT CLEAR BUFFERS. Impor-
tant information may be lost. Contact
factory service.
SERVICE MODE
Service Mode is a mode that allows the user to enable
or disable all of the outputs (except compressors) on the
unit, change chiller con
fi
guration setup parameters and
view all the inputs to the microboard.
To enter Service Mode, turn the Unit Switch off and
press the following keys in the sequence shown; PRO-
GRAM, UP ARROW, UP ARROW, DOWN ARROW,
DOWN ARROW, ENTER. Service Mode will time out
after 30 minutes and return to normal control mode, if
the panel is accidentally left in this mode. Otherwise,
turning the unit switch on will take the panel out of
Service Mode.
SERVICE MODE – OUTPUTS
After pressing the key sequence as described, the control
will enter Service Mode permitting the
outputs (except
compressors), operating hours, refrigerant type, expan-
sion valve type, and start/hour counters
to be viewed/
modi
fi
ed. The ENTER/ADV key is used to advance
through the outputs. Using the
↑
and
↓
(UP/DOWN ) ar-
row keys will turn the respective digital output on/off
or modify the value.
Following is the order of outputs that will appear as the
ENTER/ADV key is pressed:
SYS 1 COMP 1 STATUS TB7-2 IS:
SYS 1 LLSV STATUS TB7-3 IS:
SYS 1 COMP 2 STATUS TB7-4 IS:
I
I N I T I A L I Z E H I S T O R Y
E
N
T
E
R = Y
E
S
S Y S 1 L L S V S T A T U S
T
B
10
- 3 I
S O
F
F
Summary of Contents for YCAL0019
Page 55: ...FORM 150 67 NM2 209 55 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12699D...
Page 57: ...FORM 150 67 NM2 209 57 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12693C...
Page 59: ...FORM 150 67 NM2 209 59 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD 12198...
Page 61: ...FORM 150 67 NM2 209 61 JOHNSON CONTROLS 5 5 LD12702 ELEMENTARY WIRING DIAGRAM CON T...
Page 63: ...FORM 150 67 NM2 209 63 JOHNSON CONTROLS 5 5 LD12696 ELEMENTARY WIRING DIAGRAM CON T...
Page 65: ...FORM 150 67 NM2 209 65 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12703B...
Page 67: ...FORM 150 67 NM2 209 67 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12697B...