FORM 150.67-NM2 (209)
183
JOHNSON CONTROLS
9
Analog Inputs – Pressure
Refer to the unit wiring diagram. Pressure inputs are
connected to the microboard on plugs J7 and J9. These
analog
inputs represent varying dc signals corresponding
to varying pressures. All voltages are in reference to the
unit case (ground).
System 1 discharge and suction pressures will be
connected to J7 of the microboard. System 2 discharge
and suction pressure transducers will be connected to
J9 of the microboard.
The discharge transducers are optional on all units. If the
discharge transducers are not installed, no connections
are made to the microboard and the discharge pressure
readout on the display would be zero.
The suction pressure transducers are standard on all
YCAL’s. The suction pressure transducers have a range
of 0 to 400 PSIG. The output will be linear from 0.5VDC
to 4.5VDC over the 400 PSIG (27.5 barg) range.
The discharge transducers have a range from 0 to 650
PSIG. The output will be linear from 0.5VDC to 4.5VDC
over the 600 PSIG (41.25 barg) range. Following is the
formula that can be used to verify the voltage output of
the transducer. All voltage reading are in reference to
ground (unit case).
V = (Pressure in PSIG x .01) + .5
or
V = (Pressure in BARG x .145) + .5
where V = dc voltage output
Pressure = pressure sensed by transducer
The I/O board connections for the Discharge Trans-
ducers:
System 1 Discharge Transducer
J7-6 = +5VDC regulated supply to transducer.
J7-11 =VDC input signal to the microboard. See
the formula above for voltage readings
that correspond to specifi c discharge
pressures.
J7-7 = +5VDC return
J7-2 = drain (shield connection = 0VDC)
System 2 Discharge Transducer
J9-6 = +5VDC regulated supply to transducer.
J9-11 = VDC input signal to the microboard. See
the formula above for voltage readings
that correspond to specifi c discharge
pressures.
J9-7 = +5VDC return
J9-2 = drain (shield connection = 0VDC)
TABLE 33 –
PRESSURE TRANSDUCERS
0-400 PSIG SUCTION
PRESSURE TRANSDUCER
0-600 PSIG DISCHARGE
PRESSURE TRANSDUCER
PRESSURE
PSIG
VOLTAGE
VDC
PRESSURE
PSIG
VOLTAGE
VDC
0
0.5
0
0.5
50
1.0
75
1.0
100
1.5
150
1.5
150
2.0
225
2.0
200
2.5
300
2.5
250
3.0
375
3.0
300
3.5
450
3.5
350
4.0
525
4.0
400
4.5
600
4.5
RED WIRE = 5V, BLACK WIRE = 0V, WHITE/GREEN WIRE = SIGNAL
TEST POINTS:
Suction Pressure:
System 1: ...............................................Microboard J7-10 to J7-9
System 2: ...............................................Microboard J9-10 to J9-9
Discharge Pressure:
System 1: ...............................................Microboard J7-11 to J7-7
System 2: ...............................................Microboard J9-11 to J9-7
Summary of Contents for YCAL0019
Page 55: ...FORM 150 67 NM2 209 55 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12699D...
Page 57: ...FORM 150 67 NM2 209 57 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12693C...
Page 59: ...FORM 150 67 NM2 209 59 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD 12198...
Page 61: ...FORM 150 67 NM2 209 61 JOHNSON CONTROLS 5 5 LD12702 ELEMENTARY WIRING DIAGRAM CON T...
Page 63: ...FORM 150 67 NM2 209 63 JOHNSON CONTROLS 5 5 LD12696 ELEMENTARY WIRING DIAGRAM CON T...
Page 65: ...FORM 150 67 NM2 209 65 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12703B...
Page 67: ...FORM 150 67 NM2 209 67 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12697B...