JOHNSON CONTROLS
184
FORM 150.67-NM2 (209)
Service and Troubleshooting
FIG. 37 –
I/O BOARD RELAY CONTACT
ARCHITECTURE
LD12722
The suction transducers have a range from 0 to 400 PSIG
(27.5 barg). The output will be linear from 0.5VDC to
4.5VDC over the 400 PSIG (27.5 barg) range. Following
is a formula that can be used to verify the voltage output
of the transducer. All voltage reading are in reference to
ground (unit case).
V = (Pressure in PSIG x .02) + .5
or
V = (Pressure in barg x .29) + .5
where V = dc voltage input to micro
Pressure = pressure sensed by transducer
Following are the I/O board connections for the Suction
Transducer:
System 1 Suction Transducer
J7-5 = +5VDC regulated supply to transducer.
J7-10 = VDC input signal to the microboard.
See the formula above for voltage readings that
correspond to specifi c suction pressures.
J7-9 = +5VDC return
J7-1 = drain (shield connection = 0VDC)
System 2 Suction Transducer
J9-5 = +5VDC regulated supply to transducer.
J9-10 = VDC input signal to the microboard.
See the formula above for voltage readings that
correspond to specifi c suction pressures.
J7-9 = +5VDC return
J7-11 = drain (shield connection = 0VDC)
Digital Outputs
Refer to the unit wiring diagram and Fig. 37. The digital
outputs are located on TB7, TB8, and TB9 and TB-10 of
the microboard. ALL OUTPUTS ARE 120VAC with the
exception of TB8-6 to TB8-7 which are the contacts that
can be used for a remote evaporator pump start signal.
The voltage applied to either of these terminals would
be determined by
fi
eld wiring.
Each output is controlled by the microprocessor by
switching 120VAC to the respective output connection
energizing contactors, evaporator heater, and solenoids
according to the operating sequence
(see Fig. 37)
.
120VAC is supplied to the I/O board via connections
at TB7-1, TB7-6, TB10-1, TB10-6, TB8-1 and TB9-1.
Fig. 37 illustrates the relay contact architecture on the
microboard.
SYS 1
COMP 1
TB7-2
SYS 1
COMP 2
TB7-4
SYS 1
COMP 3
TB7-5
TB7-3
LLSV 1
TB8-6
EVAP
PUMP
TB8-7
TB7
SYS 2
HGSV
TB10-7
SYS 2
FAN 2
TB10-8
TB10-9
TB10-10 SYS 2
FAN 4
TB10
TB8
TB10
SYS 2
COMPR 1 (4)
TB10-2
LLSV 2
TB10-3
SYS 2
COMPR 2 (5)
TB10-4
SYS 2
COMPR 3 (6)
TB10-5
TB7
SYS 1
HGSV
TB7-7
SYS 1
FAN 1
TB7-9
SYS 1
FAN 3
TB7-10
TB7-8
SYS 1
FAN 2
TB8-2
HEAT EXCH
HEATER
Summary of Contents for YCAL0019
Page 55: ...FORM 150 67 NM2 209 55 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12699D...
Page 57: ...FORM 150 67 NM2 209 57 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12693C...
Page 59: ...FORM 150 67 NM2 209 59 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD 12198...
Page 61: ...FORM 150 67 NM2 209 61 JOHNSON CONTROLS 5 5 LD12702 ELEMENTARY WIRING DIAGRAM CON T...
Page 63: ...FORM 150 67 NM2 209 63 JOHNSON CONTROLS 5 5 LD12696 ELEMENTARY WIRING DIAGRAM CON T...
Page 65: ...FORM 150 67 NM2 209 65 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12703B...
Page 67: ...FORM 150 67 NM2 209 67 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12697B...