FORM 150.67-NM2 (209)
191
JOHNSON CONTROLS
10
TABLE 36 –
ISN TRANSMITTED DATA (CONT’D)
ISN CONTROL (CON’T)
ISN
PAGE
CHARACTER
TYPE
DATA
P38
110
Digital
Evaporator Heater
Status
P39
111
Digital
Evaporator Pump
Status
P40
112
Digital
SYS 1
Comp. 2 Run
P41
113
Digital
SYS 2
Comp. 2 Run
P42
114
Digital
SYS 1 Liquid Line
Solenoid Valve or
EEV Pilot Solenoid
P43
115
Digital
SYS 1 Hot Gas
Bypass Valve
P44
116
Digital
SYS 1
Comp. 2 Run
P45
117
Digital
SYS 2
Comp. 2 Run
P46
118
Digital
SYS 2 Liquid Line
Solenoid Valve or
EEV Pilot Solenoid
P47
119
Digital
Lead System
(0=SYS 1, 1=SYS 2)
P48
120
Digital
SYS 1
Comp.3 Run
P49
121
Digital
SYS 2
Comp. 3 Run
P50
122
Digital
Chilled Liquid Type
(0=Water, 1=Glycol)
P51
123
Digital
Ambient Control Mode
(0=Std. Ambient,
1=Low Ambient)
P52
124
Digital
Local/Remote
Control Mode
(0=Local,
1=Remote)
P53
125
Digital
Units
(0=Imperial, 1= SI)
P54
126
Digital
Lead/Lag Control
Mode
(0=Manual,1= Remote)
P55
127
Digital
----
P56
128
Coded
* SYS 1
Operational Code
P57
129
Coded
* SYS 1
Fault Code
P58
130
Coded
* SYS 2
Operational Code
P59
131
Coded
* SYS 2
Fault Code
P60
132
Coded
----
ISN
PAGE
CHARACTER
TYPE
DATA
P61
133
Coded
SYS 1 Condenser
Fan Stage
P62
134
Coded
----
P63
135
Coded
SYS 2 Condenser
Fan Stage
P64
136
Coded
----
P65
137
Coded
Unit Control Mode
(0=Leaving Water,
1=Return Water,
2=Discharge Air,
3=Suction Press.,
4=Cooling
5=Heating)
P66
138-141
Analog
Anti-Recycle Timer
P67
142-145
Analog
Leaving Chilled Liquid
Temp. Cutout
P68
146-149
Analog
Low Ambient
Temp. Cutout
P69
150-153
Analog
----
P70
154-157
Analog
Low Suction
Pressure Cutout
P71
158-161
Analog
High Discharge
Pressure Cutout
P72
162-165
Analog
Setpoint
P73
166-169
Analog
Cooling Range
P74
170-173
Analog
----
P75
174-177
Analog
----
P76
178-181
Analog
SYS 1 Discharge
Temp.
(EEV Only-Optional)
P77
182-185
Analog
SYS 1 Discharge
Superheat
(EEV Only- Optional)
P78
186-189
Analog
SYS 2 Discharge
Temp.
(EEV Only- Optional)
P79
190-193
Analog
SYS 2 Discharge
Superheat
(EEV Only- Optional)
P80
194
Digital
----
P81
195
Digital
----
P82
196
Digital
----
P83
197
Digital
----
P84
198
Digital
----
Summary of Contents for YCAL0019
Page 55: ...FORM 150 67 NM2 209 55 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12699D...
Page 57: ...FORM 150 67 NM2 209 57 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12693C...
Page 59: ...FORM 150 67 NM2 209 59 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD 12198...
Page 61: ...FORM 150 67 NM2 209 61 JOHNSON CONTROLS 5 5 LD12702 ELEMENTARY WIRING DIAGRAM CON T...
Page 63: ...FORM 150 67 NM2 209 63 JOHNSON CONTROLS 5 5 LD12696 ELEMENTARY WIRING DIAGRAM CON T...
Page 65: ...FORM 150 67 NM2 209 65 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12703B...
Page 67: ...FORM 150 67 NM2 209 67 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12697B...