JOHNSON CONTROLS
52
FORM 150.67-NM2 (209)
Technical Data
It is possible that multiple sources of power can be supplying the unit power panel. To pre-
vent serious injury or death, the technician should verify that NO LETHAL VOLTAGES are
present inside the panel AFTER disconnecting power, PRIOR to working on equipment.
The unit evaporator heater uses 120VAC. Disconnecting 120VAC power from the unit, at or
below freezing temperatures, can result in damage to the evaporator and unit as a result of
the chilled liquid freezing.
ELECTRICAL DATA
TABLE 7 –
MICRO PANEL POWER SUPPLY
VOLTAGE RANGE
VOLTAGE CODE
UNIT POWER
MIN.
MAX.
-50
380/415-3-50
342
440
UNIT VOLTAGE
UNIT
VOLTAGE
CONTROL
POWER
MCA
NOTE A
OVER CURRENT PROTECTION,
SEE NOTE B
NF DISC Sw
MIN
MAX
MODELS w/o
CONTROL
TRANS
115-1-60/50
15A
10A
15A
30 A / 240V
-50
380/415-1-60
15A
10A
15A
30A / 415V
A. Minimum #14 AWG, 75
°C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
TABLE 8 –
VOLTAGE RANGE
Summary of Contents for YCAL0019
Page 55: ...FORM 150 67 NM2 209 55 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12699D...
Page 57: ...FORM 150 67 NM2 209 57 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD12693C...
Page 59: ...FORM 150 67 NM2 209 59 JOHNSON CONTROLS 5 5 ELEMENTARY WIRING DIAGRAM CON T LD 12198...
Page 61: ...FORM 150 67 NM2 209 61 JOHNSON CONTROLS 5 5 LD12702 ELEMENTARY WIRING DIAGRAM CON T...
Page 63: ...FORM 150 67 NM2 209 63 JOHNSON CONTROLS 5 5 LD12696 ELEMENTARY WIRING DIAGRAM CON T...
Page 65: ...FORM 150 67 NM2 209 65 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12703B...
Page 67: ...FORM 150 67 NM2 209 67 JOHNSON CONTROLS 5 5 CONNECTION WIRING DIAGRAM CON T LD12697B...