SECTION 8 – UNIT OPERATION
LD12211
STANDARD CONDENSER FAN CONTROL – YCAL0019 – YCAL0033
TABLE 20 -
YCAL0019 – YCAL0033 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE
FAN
STAGE
ON*
OFF*
CONTACTOR
MICROBOARD
OUTPUT
FAN #
SYS 1
SYS 1
SYS 1
1
DP> FAN CRTL ON
PRESS
DP < FAN CTRL ON
PRESS – DIFF.PRESS
7M
TB7-9
1
2
*DP > FAN CTRL
ON PRESS AND
FAN STAGE 1 IS
ENERGIZED
**DP < FAN CTRL ON
PRESS –
DIFF. PRESS
7M
&
8M
TB7-9
&
TB7-10
1
&
3
TABLE 21 -
YCAL0019 – YCAL0033 CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY
FAN
STAGE
ON
OFF
CONTACTOR
MICROBOARD
OUTPUT
FAN #
SYS 1
SYS 1
SYS 1
1
DP > FAN CTRL
ON PRESS
DP < FAN CTRL
ON PRESS – (DIFF.
PRESS.)
7M
TB7-9
1
2
DP > FAN CTRL
ON PRESS AND
FAN STAGE 1 IS
ENERGIZED
**DP < FAN CTRL ON
PRESS – DIFF. PRESS.
7M
&
8M
TB7-9
&
TB7-10
1
&
3
* When a fan stage is turned ON, the on pressure for the next stage is increased 20 PSIG and ramped back to the programmed
on pressure over the next 20 seconds.
** When a fan stage is turned OFF (programmed on pressure minus differential), the off pressure for the next stage is decreased
20 PSIG and ramped back to the programmed off pressure minus the differential.
FAN #1
FAN #2
FIGURE 43 -
YCAL0019 – YCAL0033 FAN LOCATION (TYPICAL)
Summary of Contents for YCAL0019
Page 4: ...JOHNSON CONTROLS 4 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 69: ...69 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 71: ...71 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 229: ...229 JOHNSON CONTROLS SECTION 10 MAINTENANCE FORM 150 67 NM1 ISSUE DATE 4 28 2017 NOTES...