JOHNSON CONTROLS
54
FORM 150.67-NM1
ISSUE DATE: 4/28/2017
SECTION 5 – TECHNICAL DATA
Single-Point Field Supplied Power Wiring (See Figure 12)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused
Disconnect Switch (optional) or Circuit Breaker (optional)).
TABLE 7 -
ELECTRICAL DATA (ENGLISH)
ELECTRICAL DATA (ENGLISH)
YCAL0019_ – YCAL0066_
(Without Pump)
MODEL
YCAL
VOLT
60 Hz MCA
1
MIN N/F
DISC
MDSW
2
D.E. FUSE CKT. BKR.
5
FIELD WIRING LUGS
6
TERMINAL BLOCK (std)
FIELD WIRING LUGS
6
NF DISC. SWITCH (opt)
FIELD WIRING LUGS
6
CIRCUIT BREAKER (opt)
MIN. MAX
4
MIN. MAX LUGS/
PHASE LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
LUGS/
PHASE
LUG WIRE RANGE
0019
200 101 150 125 125 125 125
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
230 94
100 110 125 110 125
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
380 54
60
60
70
60 70
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
460 45
60
50
60
50 60
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
575 36
60
40
50
40 50
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
0022
200 108 150 125 150 125 150
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
230 100 150 125 125 125 125
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
380 58
60
70
80
70 80
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
460 48
60
60
60
60 60
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
575 39
60
45
50
45 50
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
028
200 136 150 175 175 175 175
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
230 136 150 150 175 175 175
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
380 81
100
90 110 110 110
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
460 65
100
80
90
90 90
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
575 55
60
70
70
70 70
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
0033
200 151 200 175 200 175 200
1
6 AWG – 350 kcmil 1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
230 140 150 175 175 175 175
1
6 AWG – 350 kcmil 1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
380 81
100
90 110 90 110
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
460 67
100
80
90
80 90
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
575 54
60
60
70
60 70
1
14 AWG – 2/0
1
14 AWG – 1/0
1
14 AWG – 1/0
0043
200 224 250 250 250 250 250
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
230 209 250 225 250 225 250
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
380 121 150 150 150 150 150
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
460 99
150 110 110 110 110
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
575 80
100
90
90
90 90
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
0046
200 228 250 250 250 250 250
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
230 212 250 225 250 225 250
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
380 123 150 150 150 150 150
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
460 101 150 110 110 110 110
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
575 81
100
90
90
90 90
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
0052
200 248 400 300 300 300 300
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
230 248 400 300 300 300 300
1
6 AWG – 350 kcmil 2
*(2) 3/0 – 250 kcmil
2
*(2) 3/0 – 250 kcmil
380 132 150 150 150 150 150
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
460 114 150 125 125 125 125
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
575 96
150 110 110 110 110
1
14 AWG – 2/0
1
4 AWG – 300 kcmil
1
6 AWG – 350MCM
Summary of Contents for YCAL0019
Page 4: ...JOHNSON CONTROLS 4 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 67 NM1 ISSUE DATE 4 28 2017 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 69: ...69 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 71: ...71 JOHNSON CONTROLS SECTION 5 TECHNICAL DATA FORM 150 67 NM1 ISSUE DATE 4 28 2017 5 5...
Page 229: ...229 JOHNSON CONTROLS SECTION 10 MAINTENANCE FORM 150 67 NM1 ISSUE DATE 4 28 2017 NOTES...