FORM 150.40-NM20
45
YORK INTERNATIONAL
be ignored by the Micro Logic Board. Closure longer than
11 seconds will be treated as 11 seconds.
The contact closure corresponds to a positive offset
(rise) from the Setpoint on the panel. I sec. = +0° offset
and 11 sec. = +15° or offset = 1.5 (time closed – 1 sec.).
For example: A Setpoint of 51° on the panel and a con-
tact closure of 4.33 sec. will result in an offset of +5°.
This raises the RWT Setpoint to 56°F.
To maintain a remote setpoint, the EMS Pulse Width
Modulation input (terminals 11 and 12) on the Digital
Input Board must be refreshed every 30 minutes or less
(20 minutes is recommended). In other words, to main-
tain the 56°F RWT setpoint, the contacts between ter-
minals 11 and 12 must be closed for a period of 4.33
seconds every 20 minutes. If this is not refreshed at
least every 30 minutes, the Micro Logic Board will take
this as a signal to change the RWT setpoint back to the
original setpoint of 51° on the Control Panel.
(YCHA120, 150, 175, & 200)
EXTERNAL SYSTEM MONITORING AND
DIAGNOSTICS (OPTIONAL)
RS 232 (or equivalent) SERIAL COMMUNICATION
OUTPUT PORT
This port on the bottom right of the Logic Board (J6)
allows service personnel to obtain a printout of unit con-
“OPTIONAL” REMOTE UNLOADING AND DEMAND
LIMITING
A forced unload of the system, independent of water
temperature demand, can be accomplished by closing
a dry contact connected between terminals 9 & 10 of
the optional Digital Input Board. This control feature
forces turn-off of the lag compressor. Note: J9 must
also be placed IN or Switch 4 must be in the ON posi-
tion on the Micro Logic Board. See Fig. 20 and 21.
ANNUNCIATION ALARM CONTACTS (OPTIONAL)
YORK can supply alarm contacts which will de-energize to
function as a warning if unit malfunction occurs. A 28 volt
external alarm circuit (by others) must be wired into the
YORK supplied alarm circuit. If the alarm circuit is applied
to chillers used for critical duty (such as process duty, or
cooling other critical equipment) and the alarm circuit should
fail to function, YORK will not be liable for damages. Any
inductive devices (relays) wired into the Alarm circuitry must
be suppressed. Use P/N 031-00808B suppressor.
ditions at any time. To make use of this option, contact
YORK Service or Marketing for recommended printers.
A printout can be requested by pressing the “Press To
Print” pushbutton on the Control Panel. This allows ser-
vice personnel or the customer to obtain system pa-
rameters on a periodic basis.*
A print example is shown below.
YORK RECIPROCATING CHILLER
MICROCOMPUTER CONTROL CENTER
SYSTEM STATUS
NO SYSTEM FAULTS
RETURN WATER TEMPERATURE
55.4 DEG F
LEAVING WATER TEMPERATURE
44.0 DEG F
SYSTEM 1 OIL TEMPERATURE
131.9 DEG F
SYSTEM 2 OIL TEMPERATURE
130.8 DEG F
LOW WATER TEMP CUTOUT
36.0 DEG F
TEMPERATURE SETPOINT
54.0 DEG F
OUTSIDE AIR TEMPERATURE
090.2 DEG F
LOW AMBIENT TEMP CUTOUT
35.0 DEG F
SYSTEM 1 MOTOR CURRENT
087 %FLA
SYSTEM 1 SUCTION PRESSURE
066 PSIG
SYSTEM 1 OIL PRESSURE
044 PSID
SYSTEM 1 DISCHARGE PRESSURE
197 PSIG
SYSTEM 2 MOTOR CURRENT
087 %FLA
SYSTEM 2 SUCTION PRESSURE
059 PSIG
SYSTEM 2 OIL PRESSURE
051 PSID
SYSTEM 2 DISCHARGE PRESSURE
191 PSIG
LOW SUCTION PRESSURE CUTOUT
044 PSIG
TEMPERATURE CONTROL RANGE
54.0 DEG F
TO
48.0 DEG F
SYSTEM 1 LIQUID LINE SOL
NO
SYSTEM 2 LIQUID LINE SOL
NO
SYSTEM 1 LOADED
NO
SYSTEM 2 LOADED
NO
RUN PERMISSIVE
YES
* Once the printout is obtained, the printer should be disconnected from the panel at J6.
Summary of Contents for YCAQ10
Page 20: ...YORK INTERNATIONAL 20 LD01779 YCHA100 FIG 9 WIRING DIAGRAM YCHA100...
Page 21: ...FORM 150 40 NM20 21 YORK INTERNATIONAL YCHA100 LD01779 D...
Page 22: ...YORK INTERNATIONAL 22 LD01780 L YCHA100 FIG 9 Continued...
Page 23: ...FORM 150 40 NM20 23 YORK INTERNATIONAL LD01780 R YCHA100...
Page 24: ...YORK INTERNATIONAL 24 YCHA100 LD01781 FIG 9 Continued...
Page 25: ...FORM 150 40 NM20 25 YORK INTERNATIONAL LD01782 YCHA100...
Page 46: ...YORK INTERNATIONAL 46 LD01787...
Page 47: ...FORM 150 40 NM20 47 YORK INTERNATIONAL LD01788...
Page 48: ...YORK INTERNATIONAL 48 LD01789...
Page 49: ...FORM 150 40 NM20 49 YORK INTERNATIONAL LD01790...
Page 50: ...YORK INTERNATIONAL 50 LD01791...
Page 51: ...FORM 150 40 NM20 51 YORK INTERNATIONAL LD01792...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......