FORM 150.40-NM20
73
YORK INTERNATIONAL
YCHA RECIP. CHILLER
CONDENSOR FAN OPERATION
Some questions have arisen on YCHA Condensor Fan Operation. The confusion seems to be concerning the
temperature/pressure control scheme and whether temperature or pressure should be in command.
Temperatures Above 55°F As Sensed By the OAT (Outdoor Ambient Temperature) Sensor
Fan cycling will be by temperature control only, Discharge pressure will have no effect. Above 55°F. 4 sec. after the
respective compresssor starts, Fans E and F (Compr. 1) or Fans C and D (Compr. 2) will come on. Thirty sec. after
the respective compressor starts, Fans G and H(Compr. 1) or Fans A and B (Compr. 2) will come on. These fans will
remain on, regardless of discharge pressure or loading, until the respective compressor stops or temperature drops
below 55°F. Note: YCHA 120’s will not have Fan G.
Temperatures 35°F to 55°F As Sensed By the OAT (Outdoor Ambient Temperature) Sensor
In this range, 2 fans on each system are cycled by temperature control only. Discharge pressure will have no
effect on these 2 fans. Four (4) seconds after the respective compressor starts, Fans E and F (Compr. 1) or Fans
C and D (Compr. 2) will come on. These fans will remain on, regardless of discharge pressure or loading, until the
respective compressor stops or temperature drops below 35°F.
The other two fans on each system are cycled when the respective compressor is running according to discharge
pressure only. Fans G and H (Compr. 1) or Fans A and B (Compr. 2) will cycle according to table below until
temperature as sensed by the OAT sensor rises above 55°F, until the respective compressor stops, or temperature
drops below 35°F. Note: YCHA 120’s will not have Fan G.
Temperatures Below 35°F as Sensed By The OAT (Outdoor Ambient Temperature) Sensor
Below 35°F a Low Ambient Kit option must be installed. This kit will affect fan cycling below 35°F and 35°F to 55°F.
Details on this option will be discussed in another Service Bulletin. Without this kit, the chiller will not operate below
35°F.
If any doubts arise concerning the temperature the OAT sensor is sensing, display a Code 06 on the Micro Panel
Display. This display indicates the temperature sensed by the OAT sensor located outside on the back side of the
Logic section of the control panel. It should coincide with a thermometer located in the same location ± 10°F.
FAN
FANS
DlSCHARGE PRESSURE
SYSTEM
CONTACTOR
CONTROLLED
TO CYCLE FANS
“ON”
“OFF”
1
5M
E, F
260 LB.
190 LB.
6M
G, H
280 LB.
210 LB.
2
7M
C, D
260 LB.
190 LB.
8M
A, B
280 LB.
210 LB.
Summary of Contents for YCAQ10
Page 20: ...YORK INTERNATIONAL 20 LD01779 YCHA100 FIG 9 WIRING DIAGRAM YCHA100...
Page 21: ...FORM 150 40 NM20 21 YORK INTERNATIONAL YCHA100 LD01779 D...
Page 22: ...YORK INTERNATIONAL 22 LD01780 L YCHA100 FIG 9 Continued...
Page 23: ...FORM 150 40 NM20 23 YORK INTERNATIONAL LD01780 R YCHA100...
Page 24: ...YORK INTERNATIONAL 24 YCHA100 LD01781 FIG 9 Continued...
Page 25: ...FORM 150 40 NM20 25 YORK INTERNATIONAL LD01782 YCHA100...
Page 46: ...YORK INTERNATIONAL 46 LD01787...
Page 47: ...FORM 150 40 NM20 47 YORK INTERNATIONAL LD01788...
Page 48: ...YORK INTERNATIONAL 48 LD01789...
Page 49: ...FORM 150 40 NM20 49 YORK INTERNATIONAL LD01790...
Page 50: ...YORK INTERNATIONAL 50 LD01791...
Page 51: ...FORM 150 40 NM20 51 YORK INTERNATIONAL LD01792...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ......
Page 83: ......
Page 84: ......
Page 85: ......
Page 86: ......
Page 87: ......
Page 88: ......
Page 89: ......
Page 90: ......
Page 91: ......
Page 92: ......
Page 93: ......
Page 94: ......
Page 95: ......
Page 96: ......
Page 97: ......
Page 98: ......
Page 99: ......