194
YORK INTERNATIONAL
FORM 201.19-NM6 (804)
TABLE 11 –
YCAS STYLE G, ACROSS THE LINE START - 50 HZ.
Micro Panel Contents
* Indicates one lead/phase through motor protector.
Model
No.
Volt.
Code
Chiller Name-
Plate RLA
No. Leads per Phase
100% FLA
Of Sys.
MP OL Value Set
0693
Sys 1 & 2
50
140
2
151
189
693
Sys 3
50
124
2
134
167
0773
Sys 1 & 2
50
140
2
151
189
0773
Sys 3
50
183
*2
198
124
0783
Sys 1 & 2
50
124
2
134
167
0783
Sys 3
50
168
*2
181
113
0873 50
168
*2
181
113
0953
50
183
*2
198
124
1063
Sys 1 & 2
50
161
2
174
217
1063
Sys 3 & 4
50
140
2
151
189
1093
Sys 1 & 2
50
183
*2
198
124
1093
Sys 3 & 4
50
140
2
151
189
1163
50
168
*2
181
113
1263
50
183
*2
198
124
Summary of Contents for YCAS
Page 43: ...43 YORK INTERNATIONAL FORM 201 19 NM6 804 5 This page intentionally left blank...
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM6 804 6 This page intentionally left blank...
Page 65: ...65 YORK INTERNATIONAL FORM 201 19 NM6 804 7 LD09359 Electronic Panel 035 19205 104 Rev A...
Page 81: ...81 YORK INTERNATIONAL FORM 201 19 NM6 804 LD09378 CONNECTION WIRING DIAGRAM Electronic Panel...
Page 91: ...91 YORK INTERNATIONAL FORM 201 19 NM6 804 This page intentionally left blank...
Page 147: ...147 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...
Page 205: ...205 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...