209
YORK INTERNA
TIONAL
FORM 201.19-NM6 (804)
PROCEDURE WEEKLY QUARTERLY SEMI-ANNUALLY YEAR LY
EVERY
___ HOURS
Check oil level in oil separator sight glass
X
Check liquid line sight glass / moisture indicator
X
Record system operating pressures and temperatures
X
Check programmable operating setpoints and safety cutouts
and assure they are correct for particular application.
X
Check condenser coils for dirt/debris and clean if necessary
X
Check compressor superheat on evaporator and economizer
TXV’s; Check condenser and economizer subcooling
1
X
Check compressor and evaporator heaters for operation
X
Sample compressor oil and replace oil if necessary
1
X
Leak check the chiller
1
X
Disconnect power source and lock out; Check tightness of
power wiring connections
1
X
MAINTENANCE REQUIREMENTS FOR YORK YCAS SCREW CHILLERS
*
* Reserved for customer use for any special site determined requirements.
1
This procedure must be performed at the speci
Þ
ed time interval by an Industry Certi
Þ
ed Technician who has been trained and quali
Þ
ed to work on this type of YORK
equipment. A record of this procedure being successfully carried out must be maintained on
Þ
le by the equipment owner should proof of adequate maintenance
be required at a later date for warranty validation purposes.
9
Summary of Contents for YCAS
Page 43: ...43 YORK INTERNATIONAL FORM 201 19 NM6 804 5 This page intentionally left blank...
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM6 804 6 This page intentionally left blank...
Page 65: ...65 YORK INTERNATIONAL FORM 201 19 NM6 804 7 LD09359 Electronic Panel 035 19205 104 Rev A...
Page 81: ...81 YORK INTERNATIONAL FORM 201 19 NM6 804 LD09378 CONNECTION WIRING DIAGRAM Electronic Panel...
Page 91: ...91 YORK INTERNATIONAL FORM 201 19 NM6 804 This page intentionally left blank...
Page 147: ...147 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...
Page 205: ...205 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...