CAUTION:
No Controls (relays, etc.) should be mount ed in the Smart Panel
en clo sure or con nect ed to pow er sup plies in the control pan el. Ad-
ditionally, con trol wir ing not con nect ed to the Smart Panel should not
be run through the cabinet. This could re sult in nui sance faults.
CAUTION:
Any inductive devices (re lays) wired in series with the fl ow switch
for start/stop, into the Alarm cir cuit ry, or pilot relays for pump
start ers wired through mo tor contactor aux il ia ry con tacts must be
sup pressed with YORK P/N 031-00808-000 sup pres sor across the
re lay/contactor coil.
Any contacts con nect ed to fl ow switch inputs or BAS in puts on
ter mi nals 13 - 19 or TB3, or any oth er ter mi nals, must be sup-
pressed with a YORK P/N 031-00808-000 sup pres sor across the
re lay/con tac tor coil.
CAUTION:
Control wiring con nect ed to the con trol panel should nev er be run in
the same con duit with pow er wir ing.
Summary of Contents for YCAS
Page 43: ...43 YORK INTERNATIONAL FORM 201 19 NM6 804 5 This page intentionally left blank...
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM6 804 6 This page intentionally left blank...
Page 65: ...65 YORK INTERNATIONAL FORM 201 19 NM6 804 7 LD09359 Electronic Panel 035 19205 104 Rev A...
Page 81: ...81 YORK INTERNATIONAL FORM 201 19 NM6 804 LD09378 CONNECTION WIRING DIAGRAM Electronic Panel...
Page 91: ...91 YORK INTERNATIONAL FORM 201 19 NM6 804 This page intentionally left blank...
Page 147: ...147 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...
Page 205: ...205 YORK INTERNATIONAL FORM 201 19 NM6 804 8 This page intentionally left blank...