FORM 201.19-CL2 (309)

4

 

JOHNSON CONTROLS

Economizer Superheat 
(Not all models are equipped with economizers)

Check economizer superheat at steady full compres-

sor load only, under conditions when the economizer 

solenoid  is  energized.    Measure  gas  temperature  on 

the economizer outlet pipe next to the expansion valve 

bulb. Measure gas pressure at the back seat port of the 

economizer service valve. Superheat as measured should 

be 10°F to 12°F (5.6°C to 6.7°C).
 

Subcooling

Check liquid subcooling at steady full compressor load 

only. It is important that all fans are running for the 

system. Measure liquid line temperature on the copper 

line beside the main liquid line service valve. Measure 

liquid pressure at the liquid line service valve. Sub-

cooling should be 12°F to 15°F (6.7°C to 8.3°C). No 

bubbles should show in the sight glass. If subcooling 

is out of range add or remove refrigerant as required. 

Do not overcharge the unit. The liquid flow to the main 

evaporator TXV is subcooled further by the economizer, 

increasing subcooling to between 22°F and 28°F (12°C 

and 15°C) at ambients above 90ºF.

General Operation

After completion of the above checks for System 1, stop 

the unit, switch “OFF” the 

SYS 1

 switch on the main 

panel microprocessor board and repeat the process for 

each subsequent system. When all run correctly, stop the 

unit, switch all applicable switches to the 

ON

 position 

and restart the unit.

Summary of Contents for YCAS0218-0328 60HZ

Page 1: ...ating charge Reference the Technical Data Section in the IOM Valves Open each compressor suction economizer and dis charge valve fully counter clockwise then close one turn of the stem to ensure opera...

Page 2: ...above 96 F 36 C the compressor heaters must be on for at least 8 hours before start up to ensure all refrigerant liquid is driven out of the compressor If the ambient temperature is below 86 F 30 C th...

Page 3: ...osition Start up Remove the locking device from the unit Auto OFF switch which prevents unauthorized starting of the unit before commissioning Press the Status key then turn the unit switch to the 1 p...

Page 4: ...ine temperature on the copper line beside the main liquid line service valve Measure liquid pressure at the liquid line service valve Sub cooling should be 12 F to 15 F 6 7 C to 8 3 C No bubbles shoul...

Page 5: ...l level should always be maintained running or not above the bottom of the lower sight glass and below the top of the upper sight glass If it is necessary to add oil connect a YORK oil pump to the cha...

Page 6: ...or Current Averaging Start Up Disabled 6 Heat Recovery Disabled Do Not Use 7 Expansion Valve Thermostatic Expansion Valve Electronic 8 Spare Spare Expansion valve electronic should always be selected...

Page 7: ...discharge condensing pressure can be found in the refriger ant temperature pressure chart use entering air temperature 30 F 17 C for normal condens ing temperature b The temperature of the liquid refr...

Page 8: ...superheat setting for a system is 10 12 F 6 7 C The superheat is calculated as the difference between the actual temperature of the returned refrigerant gas in the suction line entering the compresso...

Page 9: ...ow SYS 1 SYS 2 SYS 3 SYS 4 Economizer Gas Temp PSIG kPa Economizer Press F C Temp F C Superheat F C This superheat should only be checked in an ambient above 90 F 32 C Otherwise mid range adjustment f...

Reviews: