background image

FORM 201.19-CL2 (309)

6

 

JOHNSON CONTROLS

 

13. Be certain all water temp sensors are inserted 

completely  in  their  respective  wells  and  are 

coated with heat conductive compound.

  14.Assure that evaporator EEV bulbs are strapped 

onto the suction lines at 4 or 8 o’clock posi-

tions. 

  15. Assure  that  the  15  ton  economizer  TXV 

bulbs   are  strapped  onto  the  compressor 

economizer supply lines at 4 or 8 o’clock posi-

tions.

  16. Assure that the Flow Switch is properly installed, 

wired correctly, and working.

  17. Assure bolts through compressor feet to bottom 

frame rails are removed.

PAnEL CHECkS

(Power On – Both System Switches “OFF”)

  1.  Apply 3-phase power and verify its value.

  2.  Apply 115VAC and verify its value on the ter-

minal block in the lower left of the Power Panel. 

Make the measurement between terminals 5 and 

2. The voltage should be /- 10%.

  3.  Assure the heaters on each compressor are on. 

Allow the compressor heaters to remain on a 

minimum of 24 hours before start- up. This is 

important to assure that no refrigerant is in the 

compressor oil at start-up!

  4.  Program the dip switches on the microprocessor 

board for the desired operating requirements. 

OPEN  =  Left  side  of  switch  pushed  down. 

CLOSED = Right side of switch pushed down.

SwItCH

SwItCH "OPEn" 

SEttIng

SwItCH "CLOSED" 

SEttIng

1

Water Cooling

Glycol Cooling

2

Standard Ambient 

Control

Low Ambient Control

3

Refrigerant R-407C

Refrigerant R-22

4

Do Not Use

YCAS

5

Do Not Use

Motor Current 

Averaging (Start-Up) 

Disabled

6

Heat Recovery 

Disabled

Do Not Use

7

Expansion Valve 

Thermostatic

Expansion Valve 

Electronic*

8

Spare

Spare

*Expansion valve electronic should always be selected when an 

  EEV is installed.

Verify the selections by pressing the OPTIONS Key on 

the control panel. Check them off in the chart above.

Damage to the chiller could result if 

switches  are  improperly  pro-

grammed.

 

  5.  Program the required operating values into the 

micro for cut-outs, safeties, etc. and record them 

in the chart below. 

 

  Record programmed values in the chart below.

PROgRAmmED VALUES

Display Language  = _____________________________   

Discharge Press Cutout =  _______________ PSIG (kPa)

Discharge Press Unload =  _______________ PSIG (kPa)

Suction Press Cutout =  _________________ PSIG (kPa)

High Amb Cutout =   ________________________°F (°C)

Low Amb Cutout =  _________________________°F (°C)

Leaving Chilled Liquid Temp Cutout =  __________°F (°C)

High Motor Current Unload =  _________________ % FLA

Anti-Recycle Time =   ________________________ Secs

Local / Remote Mode =  __________________________

Display Units  =     _______________________________

Lead / Lag Control =   ____________________________

Power Failure Restart  =  _________________________

Suction Superheat Setpoint  =   _______________°F (°C)

  6.  Program the Chilled Liquid Setpoint/Range and 

record:

 

  Setpoint =  __________________ °F (°C)

 

  Range  =  

+/-  

________________ °F (°C)

 

 

 

  Keep  in  mind  that  the  setpoint  temperature 

displayed by the micro should equal the desired 

leaving water temperature.

  7.  Assure that the CLK jumper J18 on the Micro-

processor Board is in the ON position (Top 2 

pins).

  8.  Set the Time and Date.

Summary of Contents for YCAS0218-0328 60HZ

Page 1: ...ating charge Reference the Technical Data Section in the IOM Valves Open each compressor suction economizer and dis charge valve fully counter clockwise then close one turn of the stem to ensure opera...

Page 2: ...above 96 F 36 C the compressor heaters must be on for at least 8 hours before start up to ensure all refrigerant liquid is driven out of the compressor If the ambient temperature is below 86 F 30 C th...

Page 3: ...osition Start up Remove the locking device from the unit Auto OFF switch which prevents unauthorized starting of the unit before commissioning Press the Status key then turn the unit switch to the 1 p...

Page 4: ...ine temperature on the copper line beside the main liquid line service valve Measure liquid pressure at the liquid line service valve Sub cooling should be 12 F to 15 F 6 7 C to 8 3 C No bubbles shoul...

Page 5: ...l level should always be maintained running or not above the bottom of the lower sight glass and below the top of the upper sight glass If it is necessary to add oil connect a YORK oil pump to the cha...

Page 6: ...or Current Averaging Start Up Disabled 6 Heat Recovery Disabled Do Not Use 7 Expansion Valve Thermostatic Expansion Valve Electronic 8 Spare Spare Expansion valve electronic should always be selected...

Page 7: ...discharge condensing pressure can be found in the refriger ant temperature pressure chart use entering air temperature 30 F 17 C for normal condens ing temperature b The temperature of the liquid refr...

Page 8: ...superheat setting for a system is 10 12 F 6 7 C The superheat is calculated as the difference between the actual temperature of the returned refrigerant gas in the suction line entering the compresso...

Page 9: ...ow SYS 1 SYS 2 SYS 3 SYS 4 Economizer Gas Temp PSIG kPa Economizer Press F C Temp F C Superheat F C This superheat should only be checked in an ambient above 90 F 32 C Otherwise mid range adjustment f...

Reviews: