18
YORK INTERNATIONAL
FORM 201.19-NM7 (804)
TABLE 1 –
MOTOR PROTECTOR DIP SWITCH SETTING ACROSS-THE-LINE - 50 HZ
* Indicates one lead/phase through motor protector.
Product Description
Model
No.
Volt.
Code
Chiller
Name- -
Plate RLA
No. Leads
per Phase
Motor Protector
MP OL
Value Set
Dip Switch Settings on MP
128
64
32
16
8
4
2
1
0295
50
79
1
107
0
1
1
0
1
0
1
1
0335
Sys 1
50
115
1
155
1
0
0
1
1
0
1
1
0335
Sys 2
50
79
1
107
0
1
1
0
1
0
1
1
0375
50
115
1
155
1
0
0
1
1
0
1
1
0425
50
106
1
143
1
0
0
0
1
1
1
1
0475
SYS 1
50
148
1
200
1
1
0
0
1
0
0
0
0475
SYS 2
50
106
1
143
1
0
0
0
1
1
1
1
0515
50
148
1
200
1
1
0
0
1
0
0
0
0555
SYS 1
50
188
*2
127
0
1
1
1
1
1
1
1
0555
SYS 2
50
148
2
200
1
1
0
0
1
0
0
0
0575
50
188
2
127
0
1
1
1
1
1
1
1
0605
50
173
*2
117
0
1
1
1
0
1
0
1
Summary of Contents for YCAS0295EB
Page 43: ...43 YORK INTERNATIONAL FORM 201 19 NM7 804 5 This page intentionally left blank...
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM7 804 6 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 19 NM7 804 This page intentionally left blank 7...
Page 71: ...71 YORK INTERNATIONAL FORM 201 19 NM7 804 7 LEGEND LD09241 YCAS0295 YCAS0605...
Page 73: ...73 YORK INTERNATIONAL FORM 201 19 NM7 804 7 CONNECTION DIAGRAM SYSTEM WIRING LD010030...
Page 74: ...74 YORK INTERNATIONAL FORM 201 19 NM7 804 Technical Data COMPRESSOR TERMINAL BOX LD10029...
Page 77: ...77 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...
Page 115: ...115 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...