56
YORK INTERNATIONAL
FORM 201.19-NM7 (804)
ELECTRICAL DATA
Technical Data
Suitable for:
Across-The-Line-Start
One fi eld provided power supply circuit to the unit. Field
con nec tions to factory pro vid ed Circuit Breaker in the
Options Panel. Factory con nec tions to Terminal Blocks
in each of the two Power Pan els.
OPTIONAL SINGLE-POINT POWER SUPPLY
CONNECTION TO FACTORY CIRCUIT BREAKER
OPTIONAL SINGLE-POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER –
2 COMPRESSOR UNITS
(One Field Provided Power Supply Circuit to the chiller. Field Connections to Factory Provided Circuit Breaker.
No Internal Branch Circuit Protection (Breakers) per Motor Control Center
10
.)
NOTES:
1. – – – – – – – Dashed Line indicates Field Provided Wiring.
2. The above recommendations are based on the National Electric Code and using copper connectors only.
Field wiring must also comply with local codes.
See page 58 for notes.
Technical Data
LD05551
CHILLER FIELD SUPPLIED WIRING SYSTEM #1 SYSTEM #2
MODEL
MRA
1
FACTORY SUPPLIED BREAKER COMPRESSOR FANS
11, 12
COMPRESSOR FANS
11, 12
YCAS
RATING
5,6
WIRE RANGE
7
(LUGS) RLA X-LRA QTY FLA (EA) FLA (EA) RLA X-LRA QTY FLA (EA) LRA (EA)
0295EB 227 250 # 6 - 350 79.0 552.0 3 4.8 23.0 79 552.0 3 4.8 23.0
0335EB 272 400 (2) 3/0-250 115.0 690.0 3 4.8 23.0 79 552.0 3 4.8 23.0
0375EB 317 450 (2) 3/0-250 115.0 690.0 3 4.8 23.0 115 690.0 3 4.8 23.0
0425EB 304 500 (2) 3/0-250 106.0 690.0 4 4.8 23.0 106 690.0 4 4.8 23.0
0475EB 356 600 (3) 2/0-400 148.0 857.0 4 4.8 23.0 106 690.0 4 4.8 23.0
0515EB 409 500 (2) 3/0-250 148.0 857.0 4 4.8 23.0 148 857.0 4 4.8 23.0
0555EB 459 600 (3) 2/0-400 188.0 857.0 4 4.8 23.0 148 857.0 4 4.8 23.0
0575EB 509 700 (3) 2/0-400 188.0 857.0 4 4.8 23.0 188 857.0 4 4.8 23.0
0605EB 481 600 (3) 2/0-400 173.0 857.0 5 4.8 23.0 173 857.0 5 4.8 23.0
Option
NOT
available for units with CE mark.
See page 58 for Electrical Data footnotes.
Summary of Contents for YCAS0295EB
Page 43: ...43 YORK INTERNATIONAL FORM 201 19 NM7 804 5 This page intentionally left blank...
Page 45: ...45 YORK INTERNATIONAL FORM 201 19 NM7 804 6 This page intentionally left blank...
Page 59: ...59 YORK INTERNATIONAL FORM 201 19 NM7 804 This page intentionally left blank 7...
Page 71: ...71 YORK INTERNATIONAL FORM 201 19 NM7 804 7 LEGEND LD09241 YCAS0295 YCAS0605...
Page 73: ...73 YORK INTERNATIONAL FORM 201 19 NM7 804 7 CONNECTION DIAGRAM SYSTEM WIRING LD010030...
Page 74: ...74 YORK INTERNATIONAL FORM 201 19 NM7 804 Technical Data COMPRESSOR TERMINAL BOX LD10029...
Page 77: ...77 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...
Page 115: ...115 YORK INTERNATIONAL FORM 201 19 NM7 804 7 This page intentionally left blank...