Notes:
1. Placement on a level surface free of obstructions (including snow, for winter operation) or air recirculation ensures rated performance, reliable
operation and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable air
flow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high pressure safety
cutout; however, the system designer must consider potential performance degradation. Access to the unit control center assumes the unit is
no higher than on spring isolators. Recommended minimum clearances: side to wall - 2m; rear to wall - 2m; control panel end to wall - 1.2m;
top - no obstructions allowed; distance between adjacent units - 3m. No more than one adjacent wall may be higher than the unit.
TECHNICAL DATA
DIMENSIONS - YCAV0357E/V High Efficiency SI
POWER: SINGLE POINT WITH TERMINAL BLOCK
VIEW A-A
2273
VIEW C-C
VIEW B-B
305
CONTROL ENTRY
76 WIDE X 292 HIGH
38
102
POWER ENTRY
254 WIDE X 330 HIGH
75
POWER ENTRY IS ON BOTTOM OF PANEL
B
B
C
C
16
2241
LD12413
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...