237
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
VSD OPERATION AND CONTROLS (CON'T)
The VSD fan and glycol pump will run if any of the
following conditions listed below are true, provided
the VSD has been powered up for less than 30 seconds
and the pump has not run in the last 30 seconds. The 30
second limitations prevent pump motor overheating.
·
2 and 4 Compressor Baseplate temp is > Cutout
(218°F) – 10°F.
·
3
Compressor IGBT Baseplate temp is > Cutout
(232°F ) – 10°F.
·
Pre-charge Enable 1 from the chiller Logic Board
is ON.
·
Pre-charge Enable 2 from the chiller Logic Board
is ON.
·
VSD Internal Ambient Temp > Cutout – 10°F.
·
Any compressor is running.
·
Service Mode Fan/Pump Run is enabled.
The VSD fan/glycol pump will turn off when ALL of
the following conditions are true:
·
Compressor 1/3 IGBT Baseplate temp is < Cutout
– 15°F.
·
Compressor 2/4 IGBT Baseplate temp is < Cutout
–15°F.
·
Pre-charge Enable 1 from the chiller Logic Board
is OFF.
·
Pre-charge Enable 2 from the chiller Logic Board
is OFF.
·
VSD Internal Ambient Temp < Cutout – 15°F.
·
No compressors are running.
·
Service Mode Fan/Pump is disabled.
In some cases, the condenser fans may
be turned on by the micro, when no
compressors are running, to keep the
power components and Control/VSD
Cabinet from overheating.
IGBT Module Baseplate Temperature Sensing
Each IGBT module has an internal 5Kohm thermistor
built in to measure the temperature of the module. Up
to 4 thermistors are connected to the VSD logic board
(one per compressor). The highest module temperature
of compressors 1 and 3 are sent to the logic board along
with the highest module temperature of compressors
2 and 4. If the temperature exceeds the software trip
point, the unit will shut down on a safety. See High VSD
Baseplate Temperature Fault (P. 244) for details.
VSD Internal Ambient Temperature Sensing
A National LM34 temperature sensor located on the
VSD Logic Board is used to measure the internal ambi-
ent temperature of the Control Panel/VSD enclosure. It
has an output voltage that is linearly proportional to the
temperature in degrees Fahrenheit. If the temperature
exceeds the software trip point, the unit will shut down
on a safety. See High VSD Internal Ambient Tempera-
ture Fault (Page 244) for details.
LD10636
LM 34
SENSOR
8
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...