JOHNSON CONTROLS
FORM 201.21-NM3 (616)
SYSTEM SAFETIES (FAULTS)
Sensor Failure Cutout Fault
The Sensor Failure Cutout prevents the system from
running when a critical sensor (transducer, level sen-
sor, or motor winding temp sensor) is not functioning
properly and reading out of range. This safety is checked
at start-up and will prevent the system from running if
one of the sensors has failed.
The sensor failure safety will also fault and shutdown
a system while in operation, if a safety threshold is
exceeded or a sensor reads out of range (high or low).
Following is the Status display fault message.
X indicates the specific system.
YYYYYYYY will either indicate the
system is in a “FAULT” condition and
will restart when the fault clears, or
“LOCKOUT” after 3 faults and will
not restart until the operator clears the
fault using the keypad.
ZZZZZZZZZZZ indicates the failed sensor below:
·
SUCT PRESS
·
OIL PRESS
·
DSCH PRESS
·
LEVEL SENSOR
·
MOTOR TEMP X *
*The Unit Setup Mode allows a spe-
cific motor temperature sensor to be
ignored, if it fails.
The start inhibit thresholds for each sensor are shown
in TABLE 14:
SYS X YYYYYYYY SENSOR FAILURE:
ZZZZZZZZZZZZ
TABLE 14 - START INHIBIT SENSOR
THRESHOLDS
SENSOR
LOW
THRESHOLD
HIGH
THRESHOLD
SUCTION
TRANSDUCER
0.3VDC
4.7VDC
OIL
TRANSDUCER
0.3VDC
4.7VDC
DISCHARGE
TRANSDUCER
0.3VDC
4.7VDC
LEVEL SENSOR
3.0ma
21.0ma
MOTOR TEMP.
SENSOR
0ºF
240ºF
High Motor Temperature Cutout Fault
The High Motor Temperature Cutout prevents a com-
pressor from running when its motor temperature is
too high. A system will fault and shut down when any
compressor motor temperature sensor rises above 250°F.
The system will be inhibited from starting if its motor
temperatures sensors indicate temperatures above 240°F.
If any single temperature sensor is being ignored under
the Unit Set-up Mode, that sensor will not be utilized
when evaluating motor temperature.
Below is a sample Status display fault message:
X indicates the system and YYYYYYY indicates the
system is in a “FAULT” condition and will restart when
the fault clears or “LOCKOUT” and will not restart until
the operator clears the fault using the keypad.
SYS X YYYYYYYY HIGH MOTOR TEMP
MICRO PANEL
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...