273
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
HISTORY KEY
LD10605
HISTORY
KEY
HISTORY Key Operation
The HISTORY key provides the user access to many
unit and system operating parameters captured at the
instant a unit or system safety (fault) shutdown occurs.
The history buffer will also capture system data at the
time of normal shutdowns such as cycling shutdowns.
When the HISTORY key is pressed the following screen
is displayed:
The
◄
and
►
(ARROW) keys allow choosing between
NORMAL SHUTDOWNS and FAULT SHUT-
DOWNS. “Fault” shutdowns provide information on
safety shutdowns, while “Normal” shutdowns provide
chiller cycling information on temperature (demand),
cycling, remote, system switch, etc., shutdowns that
are non-safety related shutdowns. Once the selection
is made, the √ (ENTER) key must be pressed to enter
the selection.
HISTORY
CHOOSE HISTORY TYPE
◄ ►
XXXXXXXXXXXXXXXXXXXXXXXXXXXX
NORM HIST XX 18-JUN-20004 10:34:58 AM
SYS X COOLING DEMAND SHUTDOWN
NORM HIST XX 18-JUN-20004 10:34:58 AM
YYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYYY
Normal Shutdowns History
If the NORMAL SHUTDOWNS History is selected,
the following screen will be displayed:
XX is the normal shutdown number. The display will
provide date and time of the shutdown and the reason
for the cycling shutdown (YYY….).
The operator can view any of the stored 20 single display
normal shutdown history buffers. History buffer number
1 provides the most recent shutdown information and
buffer number 20 is the oldest safety shutdown informa-
tion saved. The
◄
and
►
(ARROW) keys allow scrolling
between each of the history buffers. The
►
(ARROW)
key scrolls to the next normal history shutdown and the
◄
(ARROW) key scrolls to the previous normal history
shutdown.
The following display will typically be displayed on a
normal shutdown due to shutdown on lack of cooling
demand.
8
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...