285
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
8
Sound Limit Setpoint
PROGRAM ◄DEF XXXXX LO XXXXX HI XXXXX
SOUND LIMIT SETPOINT = XXX %
The sound limit setpoint is programmable from 0 – 100
% with a 0% default. 0% allows operating up to the
full speed capability of the unit with no sound limiting.
Typically the sound limit control setting will be pro-
grammed for 0 % unless sound limiting is utilized on the
chiller. Sound limiting will only permit the unit to run
to a frequency less than the maximum speed capability
of the unit. Programming a value of 1% would be the
minimum sound limiting that can be programmed and
100% will be the maximum. 100% will only allow the
unit speed to operate at the minimum frequency. Usu-
ally, the sound limit % will be programmed somewhere
between 0 and 100% according the limiting needed to
satisfy the sound requirements of the site. Typically,
sound limiting will be utilized in areas sensitive to noise
during night-time hours. The sound limit display will
only be present if the sound limit option is programmed
at the factory.
Default Values
A listing of the low limits, high limits, and default values
for each of the programmable values is noted in each
display and can be found in TABLE 17. Note that the
Imperial units are exact values while the Metric units
are only approximate.
PROGRAM KEY (CON'T)
TABLE 17 - PROGRAMMABLE OPERATING PARAMETERS
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
Suction Pressure Cutout
Water
Cooling
24.0 PSIG
36.0 PSIG
24.0 PSIG
1.65 Bars
2.48 Bars
1.65 Bars
Glycol
Cooling
5.0 PSIG
36.0 PSIG
24.0 PSIG
0.34 Bars
2.48 Bars
1.65 Bars
Low Ambient Temp. Cutout
-
-2°F
50.0°F
25.0°F
-18.9°C
10.0°C
2.2°C
Leaving Chilled Liquid Temp. Cutout
Water
Cooling
-
-
36.0°F
-
-
2.2°C
Glycol
Cooling
11.0°F
36.0°F
36.0°F
-11.7°C
2.2°C
2.2°C
Motor Current Limit
-
30%
103%
103%
Pulldown Motor Current Limit
-
30%
100%
100%
Pulldown Motor Current Limit Time
-
0 Min
255 Min
0 Min
Suction Superheat Setpoint
-
8.0°F
12.0°F
10.0°F
4.4°C
6.6°C
5.6°C
Unit ID Number
-
0
7
0
Sound Limit Setpoint
Sound Limit
Option Enabled
0%
100%
0%
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...