SCHEDULE
SOUND LIMIT = XXX %
MON START = 06:00 AM STOP = 10:00 PM
SOUND LIMIT SCHEDULE
The SOUND LIMIT SCHEDULE allows setting the
day and time when the user desires using the “SILENT
NIGHT” factory programmed option to limit chiller
loading and fan operation for reduced audible noise in
the surrounding area. If the SOUND LIMIT SCHED-
ULE is selected under the CHOOSE SCHEDULE
display, the following message will appear:
The Sound Limit option can be enabled and disabled
once each day or the chiller can be set to run continuous-
ly in this mode for sound limiting whenever the chiller is
operating. When sound limiting is enabled, the unit will
be limited by the Sound Limit setpoint % as set under
the PROGRAM key. XXX in the display above will
show the Sound Limit Setpoint % programmed under
the PROGRAM key. 0% will cause no speed reduction,
while 100% only allows running at minimum speed.
The START Time for a specific day (hour and minute) is
entered using the same guidelines used for the start/stop
schedules, and press the √ (ENTER) key to store it into
memory. The cursor will then move to the AM/PM
selection.
The AM/PM selection may be chosen using the
◄
(LEFT ARROW) or
►
(RIGHT ARROW) keys and
pressing √ (ENTER) key to store the value.
This process is repeated for the STOP time.
Once the schedule for a specific day is programmed and
entered, the schedule for the next day will appear. The
schedule for each day may be programmed the same or
differently.
To view the schedule without changing it, simply press
the SCHEDULE key or the
▼
(DOWN ARROW) key
until the desired day is displayed. The
▲
(UP ARROW)
key will scroll backwards to the previous screen.
If the schedule is changed for Monday,
all other days will change to the Mon-
day schedule. Be aware of this when
programming.
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...