320
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
ISN COMMUNICATIONS
GENERAL
The Chiller Control Board contains a dual UART for RS-
485 and RS-232 communications. UART1 is dedicated
to RCC and ISN communications over an RS-485 link.
UART2 is dedicated to internal communications within
the chiller. The RS-485 port is configured for 4800
baud, 1 start bit, 8 data bits, odd parity, and 1 stop bit.
Connections for ISN communications are on the Chiller
Control Board on TB1/TB2. TB2 on the MicroGateway
is utilized for ISN comms connection. P3 is RS485+,
P2 is RS485-, and USHL is the shield.
When an ISN is communicating with a MicroGateway,
always follow the guidelines provided in the YORK
MicroGateway instruction form for application to the
specific chiller model type.
ISN communications with a 2 compressor chiller
involves only 1 section of feature 54 data. ISN com-
munications with a 3 or 4 compressor chiller involves
2 sections of feature 54 to get all the data. Control pa-
rameters from the ISN as well system 1, 2, and unit data
are handled in the first section. The second section will
not be able to do any control but only receive system 3
and 4 (if applicable) data.
Received Data (Control Data)
The chiller control panel receives 8 data values from
the ISN. The first 4 are analog values and the last 4 are
digital values. These 8 data values are used as control
parameters when in REMOTE mode. When the unit is
in LOCAL mode, these 8 values are ignored. If the unit
receives no valid ISN transmission for 5 minutes it will
revert back to all local control values. TABLE 25 lists
the 8 control parameters. These values are found under
Feature 54 on the ISN.
TABLE 25 - YORK TALK CONTROL DATA
ISN PAGE
LCHLT CONTROL
P03
Setpoint
P04
ISN Current Limit
P05
ISN Sound Limit
(Remote Sound Limit Option must
be enabled or this point is ignored)
P06
-
P07
Start / Stop
P08
-
P09
-
P10
History Buffer
LD10637
MICRO PANEL
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...