321
JOHNSON CONTROLS
FORM 201.21-NM3 (616)
ISN TRANSMITTED DATA
TABLE 26 - DXST / ISN TRANSMITTED DATA ( SECTION 1 UNIT, SYS 1, SYS 2)
ISN PAGE
CHARACTER
TYPE
DXST CHILLER DATA (UNIT, Sys 1, Sys 2)
P11
8-11
Analog
Leaving Chilled Liquid Temp.
P12
12-15
Analog
Return Chilled Liquid Temp.
P13
16-19
Analog
VSD Internal Ambient Temp.
P14
20-23
Analog
Sys 1 Suction Temp.
P15
24-27
Analog
Sys 1 Discharge Temp.
P16
28-31
Analog
Outside Ambient Air Temp.
P17
32-35
Analog
Sys 1 Oil Temp.
P18
36-39
Analog
Sys 1 Oil Pressure
P19
40-43
Analog
Sys 1 Suction Pressure
P20
44-47
Analog
Sys 1 Discharge Pressure
P21
48-51
Analog
Sys 1 Compressor % Full Load Amps
P22
52-55
Analog
Sys 1 Total Run Hours
P23
56-59
Analog
Sys 1 Total Number of Starts
P24
60-63
Analog
Sys 1 Highest Motor Temp.
P25
64-67
Analog
Sys 2 Highest Motor Temp
P26
68-71
Analog
Sys 2 Oil Temp.
P27
72-75
Analog
Sys 2 Oil Pressure
P28
76-79
Analog
Sys 2 Suction Pressure
P29
80-83
Analog
Sys 2 Discharge Pressure
P30
84-87
Analog
Sys 2 Compressor % Full Load Amps
P31
88-91
Analog
Sys 2 Total Run Hours
P32
92-95
Analog
Sys 2 Total Number of Starts
P33
96-99
Analog
VSD Output Frequency
P34
100-103
Analog
Sys 1 Flash Tank Feed Valve % Open
P35
104-107
Analog
Sys 2 Flash Tank Feed Valve % Open
P36
108
Digital
Chiller Run
P37
109
Digital
Chiller Alarm
P38
110
Digital
Evaporator Heater Status
P39
111
Digital
Evaporator Pump Status
P40
112
Digital
Sys 1 Compressor Run Status
P41
113
Digital
Sys 2 Compressor Run Status
P42
114
Digital
Sys 1 Economizer Solenoid Valve Status
P43
115
Digital
Sys 2 Economizer Solenoid Valve Status
P44
116
Digital
—
P45
117
Digital
—
P46
118
Digital
—
After receiving a valid transmission from an ISN system,
the unit will transmit either operational data or history
buffer data depending on the “History Buffer Request”
in page 06. Data must be transmitted for every ISN page
under Feature 54.
If there is no value to be sent to a particular page, a zero
will be sent. TABLE 26 shows the Section 1 page listings
for System 1 & 2 and unit data and the Section 2 page
listings for System 3 & 4 and unit data.
8
Summary of Contents for YCAV0267E
Page 61: ...61 JOHNSON CONTROLS FORM 201 21 NM3 616 This intentionally left blank 6 ...
Page 73: ...73 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 6 ...
Page 89: ...89 JOHNSON CONTROLS FORM 201 21 NM3 616 6 035 20890 009 REV LOCATION LABEL CON T LD11141 ...
Page 146: ...146 JOHNSON CONTROLS FORM 201 21 NM3 616 TECHNICAL DATA This page intentionally left blank ...
Page 147: ...147 JOHNSON CONTROLS FORM 201 21 NM3 616 6 This page intentionally left blank ...
Page 247: ...247 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank ...
Page 269: ...269 JOHNSON CONTROLS FORM 201 21 NM3 616 This page intentionally left blank 8 ...
Page 289: ...289 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 317: ...317 JOHNSON CONTROLS FORM 201 21 NM3 616 8 This page intentionally left blank ...
Page 348: ...348 JOHNSON CONTROLS FORM 201 21 NM3 616 MAINTENANCE NOTES ...
Page 349: ...349 JOHNSON CONTROLS FORM 201 21 NM3 616 9 NOTES ...